com
PYROCON19
Owner’s manual & Technician Settings
Pg. 8
P01 - Temperature set point
Move DIP switch S1 located on the side of thermostat to ON position to enter
technician settings mode.
“P01” and the temperature set point will appear on display.
Use the [+] and [-] buttons to adjust the temperature set point.
Range: 14…59°F / -10…+15°C, default 37°F / +3°C
As long as the ambient temperature is lower than the temperature set point P01,
the heaters will turn ON upon receiving a positive snow signal from the snow
detector.
Temperature
set point
Technician settings
Ambient
temperature
sensor
Snow
detector
Snow
detector
Ambient
temperature
sensor
PYROSENSE-GUTTER
PYROSENSE
Cont’
The controller will read the ambient temperature from the connected sensors in
the following priority:
1. PYROSENSE – aerial sensor.
2. PYRO-GUTTER gutter sensor.
3. T2 sensor – When no aerial or gutter sensors are used.