Technician settings (Cont’)
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec
.
com
PYROCON19
Owner’s manual & Technician Settings
Pg. 15
P10 - Test conditions mode / Technician commissioning mode
Turn ON test conditions to check the functionality of the system regardless of
sensors parameters (i.e. during the summer).
In test conditions, the Ambient temperature is always -5°C/23°F.
Note: In order to trigger the system and activate the heaters, use some water to
wet the circuit on top of the snow sensor.
Press the [SELECT] and [+] buttons simultaneously.
“P10” will appear on display. The hours will blink.
Use the [+] button to enter test/commissioning mode – the word “Test” will
appear on display.
Use the [-] button to manually exit test/commissioning mode – the word
“Test” will disappear from display.
Note: If the technician did not manually exit test/commissioning mode, the unit
will automatically return to normal mode after 5 hours.
Test
conditions
mode
Cont’