gate cycling troubleshooting

Gate Symptom

Solutions (what to check)

• 

Check GATE SHUTOFF switch, it should be OFF. Turn switch ON then OFF again, possible chain drop event and switch needs
to be recycled. GATE DISABLE LED should be OFF.

• 

Check if OPEN and CLOSE Limits have been learned. Refer to “Learn Gate Positions” (see     ).

• 

Check if GATE SPEED rotary dial is set to MAX position (LED on).

• 

Gate may be too heavy for operator (check for maximum gate weight for your model operator).

• 

Check if "BATTERY IN USE" LED is ON. If so, gate is on Battery back up mode and battery is running low.

• 

Operator may be in battery back up mode. Check if “Mode 1” switches are set correctly.

• 

Check if “Gate in Motion” Alarm feature is ON (“Mode 0” switches are set correctly).

• 

Check if Power LEDs are ON on both Matrix III and Toroid box. Check if “LINK ON” LED is ON.

• 

Check if PRIMARY GATE "open RIGHT / open LEFT" switch is set properly.

• 

Check if GATE SHUTOFF switch is OFF (GATE DISABLE LED should be OFF)

• 

Check if GATE DISABLE LED is ON. If so, check if GATE DISABLE input is active.

• 

Check if “PHOTO OPEN” LED or “OPEN/CLS” LED is ON or BLINKING. If so, check entrapment sensor wiring.

• 

Check if “BATTERY IN USE” LED is ON. If so, battery may be too low and gate is kept closed (BATTERY BACK-UP MODE
switch set to “Leave Closed”).

• 

Check if Power LEDs are ON on both Matrix III and Toroid box. Check if “LINK OK” LED is ON.

• 

Check if “PHOTO CLS” LED is ON. If so, check entrapment sensor wiring and alignment.

• 

Check if any loops are active, check SAFETY LOOP or EXIT LOOP LED is ON.

• 

Check if any open command inputs are active (check if LED is ON on for: RADIO, FIRE DEPT, MAX OPEN, STRIKE,
KEYPAD/RDR). Check device connected to the input that LED light is turned ON.

• 

Check if PRIMARY GATE “open RIGHT / open LEFT” switch is set properly.

• 

Check if GATE SHUTOFF switch is OFF (GATE DISABLE LED should be OFF)

• 

Check if GATE DISABLE LED is ON. If so, check if GATE DISABLE input is active.

• 

If “OPEN ONLY“ LED or “OPEN/CLS“ LED is ON or BLINKING. If so, check entrapment sensor wiring.

• 

If “BATTERY IN USE” LED is ON and BATTERY BACK-UP MODE switch is set to “Leave Open”, then battery may be too low
and gate is kept OPEN.

• 

If “BATTERY IN USE” LED is ON and BATTERY BACK-UP MODE switch is set to “OPEN 1-TIME”, then if AC power is lost, gate
will automatically open 1 time.

• 

If “CLOSE TIMER” is OFF, then gate will not close automatically. A close command (i.e radio, close) is required to close gate.

• 

Loop detector is defective (EXIT, or SAFETY).

• 

Loop has a short or open. Measure loop resistance.

• 

If “ERD“ LED is ON, an obstruction (ERD event) is detected. If no apparent obstruction, select a less sensitive ERD setting.

• 

If “OPEN ONLY“ LED is ON, entrapment sensor is triggered.

• 

Gate Open and Close Limits have not been learned properly. Relearn limit positions using jog Right and jog Left.

• 

The magnet(s) are not installed in correct limit position on the chain.

• 

Only for OPENING gate (not during closing cycle): Check if PARTIAL OPEN feature is turned ON. Relearn partial open position
or turn off PARTIAL OPEN feature.

• 

If “LINK OK” LED is OFF, then check wiring between Matrix III and Limit sensors.

• 

Check if “OPEN/CLS” LED is ON. If so, check entrapment sensor wiring.

• 

Motor hall sensor cable may be compromised. Unplug cable from Matrix III “Motor Inputs” and ensure wires are not broken
and are crimped properly.

• 

Check if closing photocell is misaligned with reflector (check photocell connected to“PHOTO CLS” input or “OPEN/CLS” input.

• 

Check if SAFETY LOOP is set too sensitive, then gate itself triggers SAFETY loop and reopens gate. Desensitize SAFETY LOOP
detector.

• 

Use jog Right and jog Left buttons to learn new positions instead of using open or close buttons.

Gate beeps but will not open 
or close for any command 
given.
Gate moves slowly.

Gate beeps when opening 
and closing.
Gate does NOT open.

Gate does NOT close.

Gate stops prematurely and 
beeps, moves in opposite 
direction.
Gate will stop before 
reaching desired limit 
setting.

Gate stops abruptly while in 
motion.

Gate re-opens while closing.

Gate does not learn new 
magnet positions.

Use this table to help with troubleshooting AND operator LED troubleshooting on the next 2 pages.

7

20

UL 325 2018 Standard - MAX 1500 PRO/2200 PRO/F18 PRO Matrix III Install 

Version 7a

Summary of Contents for 1500 PRO

Page 1: ...om 4009963 Residential Commercial Brushless DC Slide Gate Operators Made in USA CONFORMS TO UL STD 325 MAX 1500 PRO 2200 PRO UL CLASS I II III IV MAX F18 PRO UL CLASS III IV ONLY CERTIFIED TO CAN CSA...

Page 2: ...t lors de l ouverture et de la fermeture la barri re doit tre install e dans un endroit o la barri re et les structures avoisinantes sont suffisamment loign es l une de l autre Les barriers battantes...

Page 3: ...1 Au moins un capteur de contact doit tre situ o il existe un risque de coincement ou d obstruction comme sur le bord d ouverture sur le bord de fermeture et sur les poteaux mont s sur l int rieur ou...

Page 4: ...etest the gate operator properly can increase the risk of injury or death 4 V rifiez le fonctionnement de l ouvre barri re une fois par mois Le sens de la course DOIT s inverser lorsque la barri re en...

Page 5: ...25 model classifications A Inherent entrapment protection system B1 Provision for connection of a non contact sensor photoelectric sensor or the equivalent B2 Provision for connection of a contact sen...

Page 6: ...stalled where entrapment or pinch point exist A minimum of TWO entrapment protection sensors MUST be installed ONE in EACH direction of gate travel or operator will NOT function Physical Stops Install...

Page 7: ...29 UL 325 Class of Operation MAX 1500 PRO 2200 PRO Class I II III IV MAX F18 PRO Class III IV ONLY Gate Type Vehicular Slide Gate Max Gate Length 50 ft Max Gate Weight MAX 1500 PRO 1500 lbs Level Gate...

Page 8: ...round to avoid flooding Concrete Depth Note The heavier the gate the deeper the concrete pad should be At least two feet recommended for heavier gate Secure gate operator to concrete pad with four 4 1...

Page 9: ...or is NOT parallel to gate Chain is NOT parallel to gate DO NOT mount chain bracket too high on gate NO NO YES YES YES YES Drive Gear NOTE The chain should sag no more than one 1 inch per 10 feet of t...

Page 10: ...75 7 5 7 5 6 75 Cover 1 5 4 5 6 5 8 625 12 75 Conduit Area Outside Property Inside Property Input Power Physical Stop Conduit Run Operator MUST be level Concrete Pad Check local building codes in your...

Page 11: ...heel Approx 1 5 Pulley Wheel Safety Cover Gate YES YES Modify Cover for Rear Mounting Position 16 5 Cut out cover between new hole and existing chain exit slot Make sure cuts are plumb with existing c...

Page 12: ...Amp Select Input Voltage 115VAC or 230VAC 1 1 5 V MAX Toroid Box ac input power 2 GFCI Outlet NOT provided DANGER HIGH VOLTAGE Additional Gang Box Choose either 115V or 230V setting on input AC power...

Page 13: ...r or F Bat ter y Mo dul e Ground within 3 ft of operator Any of the THREE Chassis Grounds can be used They are located next to the gear reducer DO NOT remove any existing green ground wires 1 2 3 Grou...

Page 14: ...C UL SENSOR 10K entrapment protection wiring 5 Entrapment Protection Device Options and Locations Beam 5 or LESS from CLOSED gate Conduit Entrapment Area CLOSING Direction Photocell Wall Gate Closed...

Page 15: ...Mini Edge Contact Edge Sensor ASO Edge Thin Edge MAX Edge 1 Contact Edge Sensor Test Connected Sensors Test ALL connected entrapment protection sensors using learn mode 1 Press and HOLD the STOP butt...

Page 16: ...PEN GATE SPEED MAG LOCK UL ENTRAP PRIMARY SECONDARY LINK STOP CLOSE MOTOR INPUTS CLOSE TIMER MAGLOCK DELAY JOG BATTERY TEST INPUT ERROR BATTERY BATTERY IN USE REPLACE BATTERY LEAVE CLOSED LEAVE OPEN O...

Page 17: ...ter clockwise to reduce gate sensitivity while testing ERD until desired results is attained LED remains OFF for all but position 1 IMPORTANT When satisfied with ERD adjustment cycle the gate 3 or 4 t...

Page 18: ...Detectors to HIGH sensitivity to avoid false trigger NOTE DO NOT select the PULSED output option for Loop Detectors EDI Loop Detector EDI Loop Detector Low Current Draw ON 1 2 3 4 5 6 7 8 5 Op tim um...

Page 19: ...en wired to indicated inputs MUST be LEARNED BEFORE they will be MONITORED 2 Press and HOLD the STOP button then the OPEN button together until beeping is heard learn mode begins DO NOT press the OPEN...

Page 20: ...EN OPEN 1 TIME BATTERY VOLTAGE E F 1 2 RESET MANUAL RELEASE ID PLUG LINK OK MODULE PORT MOTOR POSITION INPUTS SLIDER LIMIT SWING LIMIT OPEN ONLY NC OPEN ONLY 10K PHOTO CLS NC OPEN CLS NC GND 12VDC OUT...

Page 21: ...servicing the operator to prevent the switch from accidentally being turned ON during normal operation Plug the wire back in and turn ON the switch only while servicing the operator This can prevent...

Page 22: ...3 4 5 6 7 8 9 10 1 2 3 4 5 6 MIN MIN MAX MAX ON OFF 2 5 sec 1 5 sec OPERATOR MATRIX III OFF 3 1 14 16 MIN 16 MIN 12 9 7 3 1 14 12 9 7 UL SENSOR N C UL SENSOR 10K POWER MODE A LOOP LOOP LOOP GATE OPEN...

Page 23: ...SOR 10K POWER MODE A MODE B EXIT LOOP LOOP LOOP CENTER SAFETY GATE OPEN COM GATE CLOSED MIN MATRIX III SWING SLIDE Gate Tamper Relay The GATE TAMPER is factory set to OFF Unarmed See previous page for...

Page 24: ...IGHT JOG LEFT TAMPER IN TAMPER NO GATE DISABLE MANUAL RELEASE KEYPAD CARD GND GND GND MAX OPEN FIRE DEPT RADIO GND RADIO SIGNAL STRIKE CLOSE COM COM STOP OPEN CLS ONLY 10K OPEN CLS 10K 12VDC OUT NO CO...

Page 25: ...GND GND GND MAX OPEN FIRE DEPT RADIO GND RADIO SIGNAL STRIKE CLOSE COM COM CLS ONLY 10K OPEN CLS 10K 12VDC OUT NO COM NC ERROR 24VDC OUTPUT 12VDC OUTPUT GND GND GND LOOP PWR OFF PRIMARY LEFT ON OFF B...

Page 26: ...RI_MC Photo Cell Ac vated Fri 07 11 2014 10 57 21 INFO Radio Input Deac vated Fri 07 11 2014 10 57 21 INFO Radio Input Ac vated Fri 07 11 2014 10 56 46 WARNING PRI_MC Tamper Reported Fri 07 11 2014 10...

Page 27: ...TERY IN USE LED is ON and BATTERY BACK UP MODE switch is set to Leave Open then battery may be too low and gate is kept OPEN If BATTERY IN USE LED is ON and BATTERY BACK UP MODE switch is set to OPEN...

Page 28: ...S ONLY 10K LED is ON PHOTO CLS LED is flashing CLS ONLY 10K LED is flashing OPEN ONLY LED is ON OPEN ONLY LED is FLASHING MAX SENSE LED is ON MANUAL RELEASE RESET LED is ON but manual release is not w...

Page 29: ...flashing Loop fault condition check if SAFETY loop wires are connected into to loop input connector properly Check if SAFETY loops are wired in series Check if loop detector is inserted properly in L...

Page 30: ...a...

Page 31: ...protection device MUST be MONITORED by the gate operator Installation Steps 1 Set DIP switches on receiver 2 Install jumper on receiver 3 Wire Matrix III 12VDC OUT power to receiver 4 Wire PHOTO CLS...

Page 32: ...nd to an obstruction lower the sensitivity by turning adjustment counter clockwise Transmitter TX Secondary Matrix III Receiver RX Normally Closed PHOTO CLS NC Common GND Green LED Green LED NOComNC J...

Page 33: ......

Page 34: ...NC Power NC Jog Left Jog Right External Alarm Reset Button Dry Contact Security Device PRESS to RESET ID Plug Specific for operator type REQUIRED Maglock Solenoid Lock Motion Sensor External Jog Left...

Page 35: ...hain 7 JOG gate closed slightly and install magnet 8 Gate positions can now be learned see Plug OPEN JOG LEFT RIGHT optional magnet limit sensors CLOSING CLOSING OPENING RD OTOR VER OAD ERD MOTOR OVER...

Page 36: ...GNAL STRIKE STOP OPEN ID PLUG ERROR 24VDC OUTPUT 12VDC OUTPUT GND GND GND LOOP PWR OFF PRIMARY SECONDARY ON QUICK CLOSE OPEN LEFT O R GATE OFF 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 MIN MIN MAX MAX ON FAULT...

Page 37: ...30 UL 325 2018 Standard MAX 1500 PRO 2200 PRO F18 PRO Matrix III Install Version 7a...

Page 38: ...31 UL 325 2018 Standard MAX 1500 PRO 2200 PRO F18 PRO Matrix III Install Version 7a...

Page 39: ...32 UL 325 2018 Standard MAX 1500 PRO 2200 PRO F18 PRO Matrix III Install Version 7a...

Page 40: ...708 Tel 949 699 0220 4009963 Residential Commercial Brushless DC Slide Gate Operators Made in USA SAFETY SENSORS REQUIRED MATRIX III CONFORMS TO UL STD 325 MAX 1500 PRO 2200 PRO UL CLASS I II III IV M...

Reviews: