Master DHA 160 Operating Manual Download Page 29

A damper should be installed in the wet air duct to enable correct 
setting of the reactivation air volume during commissioning. 
The exhaust opening should have a coarse wire net.  
Reactivation air into the dehumidifier  
For  reactivation  of  the  dehumidifier  an  additional  air  volume  is 
needed. This air enters the unit along side the process air. As an 
option  the  dehumidifier  can  be  equipped  with  duct  connections 
for entering air (DHA 160 Ø125; DHA 250 2xØ80). One of them 
can be used for intake of ambient air for reactivation (DHA 250).

 

The  duct  should  be  as  short  as  possible,  requires  no  insulation, 
and  can  slope  up  or  down.  In  some  installations,  as  an 
alternative, the reactivation air can be taken from the installation 
plant room, for this alternative no duct connection is needed.  
Process  and  dry  air  with  the  dehumidifier  installed  in  the 
dehumidified room  
When  the  dehumidifier  is  installed  in  the  dehumidified  room  it 
would  normally  take  the  process  air  directly  from  the  room 
without  any  duct  system.  If  the  process  air  inlet  needs  to  be 
connected  to  a  duct  system,  the  dehumidifier  is  prepared  for 
using  a  plate  with  duct  connections.  The  dry  air  outlet  would 
normally  have  a  duct  system  designed for  distribution  of  the  dry 
air  in  the  building.  Process  and  dry  air  with  the  dehumidifier 
installed outside the dehumidified room  
When  the  dehumidifier  is  installed  in  a  separate  plant  room  all 
inlet and outlet openings are usually ducted. 
The dehumidifier takes the process air as ambient air, or as pre-
treated air (cooled/heated), or alternatively as return air from the 
dehumidified  room.  The  dry  air  from  the  dehumidifier  can  be 
connected for post treatment or ducted back to the dehumidified 
room. 
Dampers  should  be  installed  in  the  dry  and  wet  air  ducts, 
enabling correct commissioning of the air volumes.  
Duct connection for basement installation 
If  the  dehumidifier  should  be  installed  in  the  basement  it  is 
sometimes desirable to achieve a slight negative pressure in the 
basement to prevent odours from penetrating up into the building. 
In  these  circumstances  the  reactivation  air  is  taken  directly  from 
the  basement  and  the  wet  air  is  exhausted  out  from  the 
basement. This method of installation will create a small negative 
pressure. The other ducts should be installed according to ”Duct 
connection for permanent installation 
Temporary installation 
With temporary installations for water damage or building drying, 
flexible plastic ducts would normally be used instead of the spiral 
duct type. The drying  method differs depending on situation and 
construction  to  be  dried.  The  complete  room  could  be 
dehumidified,  or  just  the  damaged  part.  For  the  later  option 
plastic sheet is used to cover the damaged area, and the dry air 
is supplied under the sheet. For both options the wet air must be 
exhausted  out from  the  building  via  flexible  duct,  or  alternatively 
connected  to  the  general  exhaust  ventilation  system  for  the 
building. 
6. COMMISSIONING  
On  initial  start  up,  the  following  steps  should  be  taken  in  this 
order: 
A.  Ensure  that  the  external  isolation  switch  is  isolating  the  unit 

from the mains, or that the power plug is disconnected. 

B.  Select  the  OFF  position  on  the  main  switch  (orange)  at  the 

front of the dehumidifier. 

C.  Open  the  service  panel  on  the  top  of  the  dehumidifier  and 

ensure  no  foreign  objects  are  left  inside  the  unit  or  in  the 
electrical compartment 

D.  Make sure the air filter is installed. 
E.  Rotate  the  fan  impeller  by  hand  and  make  sure  it  can  move 

freely. 

F.  Ensure  that  the  dry  and  wet  air  dampers  are  open,  and  that 

ducts are clean and free of blockages. 

G.  Ensure that the mains supply fuse is suitably rated (10A), and 

that the fuse is of a slow kind.  

H.  Connect  the  dehumidifier  to  the  main  electrical  supply  by 

turning the isolation switch to ON, or alternatively connect the 
power plug to the socket. 

I.  Select the MAN position on the operation switch (black) of the 

dehumidifier. Switch the main switch (orange) to the ON posi-
tion  for  3-4  seconds.  Check  that  the  rotor  is  slowly  rotating, 
the  fans  are  starting,  and  that  the  orange  lamp  in  the  main 
switch lights up. Turn OFF the dehumidifier. 

J.  Mount  the  service  panel  and  ensure  it  seals  properly  to  the 

casing. 

K.  The dehumidifier is now ready for operation. 
L.  Start  the  dehumidifier  and  check  that  the  unit  is  operating  at 

the correct air volumes.  
DHA 250 
An  indication  of  correct  operation  is  if  the  ampere  meter  on 
the front of the dehumidifier indicates approximately 6 A. 

M.  From the factory the dehumidifier is electrically  wired in such 

a  way  that  when  operating  in  AUTO  mode,  the  controls 
operate  the  complete  unit  to  start  or  stop.  By  shifting  one 
terminal connection in the electrical panel the operation mode 
can be altered to operate the fan continuously. The control will 
then only operate the heater on /off, depending on the signal 
from the humidistat or other external signal. 

7.  MAINTENANCE  
NOTE ! With all maintenance and service of the dehumidifier: 
•  Switch  off  the  dehumidifier    approximately  15  minutes 

prior to opening the service panel, allowing the heater to 
cool down.
 

•  Disconnect  the  dehumidifier  from  main  electrical  supply 

by  turning  the  external  switch  to  the  off  position  or  by 
pulling out the power plug
 

The  maintenance  intervals  for  the  dehumidifier  depend  on  the 
surrounding  environment  and  installation  site.  Recommended 
maintenance intervals could therefore differ from one installation 
to  another.  Incorrect  maintenance  and  service  may  result  in 
reduced dehumidification capacity.  
Filter 
The  dehumidifier  is  equipped  with  one  common  filter  for  the 
process air and reactivation air. The filter is positioned at the inlet 
and will clean the air prior to entering the dehumidifier. 
Intervals  for  cleaning  or  replacement  of  the  filters  will  be 
determined  by  the  amount  of  dust  and  particles  in  the  air  at  the 
installation site. 
We recommend that  the filter  is  checked  at least  once a month, 
at least for the first year of a new installation. 
Never operate the dehumidifier without the filter, as the rotor can 
be damaged by dust. 
Rotor 
The rotor is maintenance free. However should it be necessary to 
clean  the  rotor  careful  use of  compressed  air  should be the first 
choice. With severe contamination the rotor can be washed with 
water. 
Cleaning  with  water  is  no  routine  matter,  please  contact 
distributor prior to this procedure. 
Check  the  rotor  bearing  and  the  rotor  surface  once  a  year. 
Electrical motors 
The  electrical  motors  are  equipped  with  ball  bearings.  The 
bearings  are  designed  to  last  the  life  of  the motor  and  therefore 
no maintenance is required. 
Check the motors once a year for any abnormal sound. 
Heater 
The  reactivation electric  heater  does not need  maintenance, but 
should  be  checked  twice  a  year  for  any  dust  or  mechanical 
damage to the heating rods. Clean with a soft brush, or vacuum 
clean  with  dust.  Gentle  use  of  compressed  air  is  another 
alternative. 
Rotor drive belt 
Check  the  belt  tensioning  at  regular  intervals.  Adjust  when 
needed  by  moving  the  tensioning  support  wheel  closer  to  the 
desiccant rotor.  
General summary of maintenance intervals 

 

F

ilt

e

R

o

to

B

e

a

ri

n

g

 

M

o

to

rs

 

R

o

to

d

ri

v

e

 

H

e

a

te

S

e

a

lin

g

s

 

On demand 

 

 

 

 

 

 

Every 6th month 

 

 

 

 

 

 

Every 12th month   

 

 

 

 

 

 
8. TRANSPORTATION 
Observe the following for transport or handling of the 
dehumidifier: 

Summary of Contents for DHA 160

Page 1: ...L HR SU NICA ZRAKA INSTRUKCIJA OBSLU IVANJA HU P R TLAN T HASZN LATI UTASIT S IT DEUMIDIFICATORE MANUALE OPERATIVO LT ORO SAUSINTUVAS EKSPLOATACIJOS INSTRUKCIJA LV GAISA SAUSIN T JS LIETO ANAS INSTRUK...

Page 2: ...Humidity operating range 100 2 Temperature operating range 0 C 30 40 3 Dry air flow m 3 h 160 290 4 Wet air flow m 3 h 40 80 5 Dehumidification rate l 24h 14 4 26 4 a phase 1 b voltage V 230 6 Power...

Page 3: ...4 5 A B C D E...

Page 4: ...BG 1 DHA 160 DHA 250 15 2 DHA 160 DHA 250 100 30 C 40 C 3 3 30 C 40 C 100 C 4 IEC OP 44 2333 IP 54 ISO F PTC 30 100 0 1 MAN AUTO 5 DHA 160 DHA 250...

Page 5: ...400 2 DHA 160 125 DHA 250 2x 80 DHA 250 6 A B OFF C D E F G H ON I MAN 3 4 ON J K L DHA 250 6A M AUTO 7 15 off...

Page 6: ...1 64 2 125 3 250 4 500 5 1000 6 2000 7 4000 8 8000 A 65 26 14 10 10 9 3 9 15 B 66 22 11 6 10 10 3 9 15 C 67 27 12 7 7 10 3 8 14 D 67 27 13 7 10 10 3 8 14 E 59 24 10 11 6 4 5 14 20 L WA dB A rel 10 12...

Page 7: ...eden z budovy 4 POPIS V ROBKU Vysou e byl navr en tak aby spl oval po adavky IEC pro stupe ochrany OP 44 Kryt p stroje Kryt vysou e e je vyroben z nerezov oceli 2333 V horn sti vysou e e se nach z pan...

Page 8: ...rick s t nebo e je p stroj vyt hnut ze z suvky B Hlavn vyp na oran ov zep edu vysou e e p epn te do polohy OFF C Otev ete servisn panel naho e vysou e e a ujist te se e se v za zen nebo v elektrick m...

Page 9: ...m p smu dB A K Korekce kalkulace dB A Hladina hluku v pokojov ch podm nk ch R 10 2 Sab 10 E EN PROBL M Probl m Mo n p ina probl mu e en dn nebo omezen vysou en Ucp n filtru Porucha elektrick ho oh va...

Page 10: ...uft adsorbiert die Feuchtigkeit von dem mit dem Kiesels uregel beschichteten Rotor Die Regenerationsluft geht durch ein Reinigungssegment des Rotors durch und k hlt das Rotormaterial ab wobei die Temp...

Page 11: ...erzeugen Andere Leitungen sind gem Leitungsanschluss bei Dauerinstallation anzuschlie en Vorl ufige Installation Bei vorl ufigen Installationen die die Beseitigung von Hochwassersch den oder die Entfe...

Page 12: ...uft an eine kurze 90 Grad Leitung angeschlossen D Auslass nur f r Trocken und Feuchtluft angeschlossen E Alle Ausl sse angeschlossen Korrektur um K dB bei ISO Frequenzband Nr Mittelfrequenz Hz Transfe...

Page 13: ...gningen 4 BESKRIVELSE AF PRODUKTET Luftaffugteren er blevet udformet p en s dan m de at den opfylder alle IEC krav for OP 44 sikkerhedsniveau Kasse Kassen er udf rt af rustfri st l 2333 P toppen af lu...

Page 14: ...er om stikket er fjernet fra stikkontakten B Flyt hovedafbryderen gul som befinder sig i fronten af luftaffugteren til OFF position C bn serviceringspanelet og tjek om der ikke ligger nogle fremmede l...

Page 15: ...t jniveau i dB A rel 10 12 W LWAO Lydeffektniveau i oktavb nd dB A rel 10 12 W K Korrektion af beregningen LWAO LWAO LWA K dB A Lydeffektniveau under normale rumforhold R 10 2 Sab 10 FEJLFINDING Fejl...

Page 16: ...ile juurdep s elektri ja mehaanilistele elementidele K ik hukuivati torude hendused on projekteeritud standardsete spiraaltorude m tmeid arvestades Rootor hukuivatil on kuivatavast materjalist valmist...

Page 17: ...kaitsmetega H hendada hukuivati toitega p rates l liti positsioonile ON v i pannes pistiku v rgukontakti I Valida hukuivati l litiga musta MAN asend Panna peal liti oran asendisse ON 3 4 sekundiks Ko...

Page 18: ...atusv imsus Filter on ummistunud Elektrilise k ttekeha rike Piiratud huvoolus Rootor ei p rle Seadme sisemine leke Muutunud huhulgad Muutunud reaktiveerimis hu temperatuur hu lekkimine Puhastada v i a...

Page 19: ...emperatura de ese aire incrementa Gracias al calentador el ctrico la temperatura del aire inicialmente calentado sigue subiendo hasta alcanzar unos 100 C En el momento en el que el aire de reactivaci...

Page 20: ...reactivaci n se recoge directamente desde el s tano mientras que el aire h medo est siendo expulsado de l Este tipo de instalaci n generar una peque a subpresi n Los dem s conductos deber an ser inst...

Page 21: ...do Dib 5 P Aire de proceso W Aire h medo D Aire seco R Aire de reactivaci n A Orificio redondo de entrada para el aire de proceso B Orificio abierto para el aire de proceso La salida de aire seco cone...

Page 22: ...n IEC standardin OP 44 suojausluokan vaatimuksia Rakenne Laitteen kotelo on valmistettu 2333 tyyppisest ruostumattomasta ter ksest Kuivaimen yl osasta l ytyy irrotettava paneeli joka antaa mahdollisuu...

Page 23: ...vaa huoltopaneeli kuivaimen yl puolelta ja varmista ettei laitteen sis n tai s hk osioon j nyt mit n asiattomia esineit D Varmista ett ilmansuodatin on asennettu paikalleen E Kierr k sin puhaltimen po...

Page 24: ...O LWA K dB A nitehotaso huoneolosuhteissa R 102 Sab 10 VIANETSINT Vika Mahdollinen syy Korjaustapa Puuttuva tai matala kuivaustehokkuus Suodatin tukossa Vastuksen vika Rajoitettu ilmavirta Roottori ei...

Page 25: ...segment de nettoyage du rotor en refroidissant ainsi le mat riau du rotor et ensuite la temp rature de cet air augmente Gr ce au radiateur lectrique la temp rature de l air pr chauff continue d augme...

Page 26: ...cave par contre l air humide y est vacu La pr sente m thode d installation va g n rer une petite valeur de pression n gative Les autres conduits doivent tre install s en conformit avec le raccord des...

Page 27: ...c t de la palette de transport 9 DONNEES CONCERNANT LE BRUIT DHA 250 Chemin du bruit Des 5 P air de processus W air humide D air sec R air de r activation A Ouverture d entr e d air de processus ouver...

Page 28: ...n be removed for service access to electrical and mechanical components All duct connections to the dehumidifier are designed for connections to standard size spiral ducts Rotor The dehumidifier has a...

Page 29: ...ampers are open and that ducts are clean and free of blockages G Ensure that the mains supply fuse is suitably rated 10A and that the fuse is of a slow kind H Connect the dehumidifier to the main elec...

Page 30: ...m condition R 102 Sab 10 FAULT FINDING MALFUNCTION POSSIBLE CAUSE OF TROUBLE CORRECTIVE ACTION None or reduced dehumidification capacity Filter clogged Electrical heater faulty Airflow reduced No rota...

Page 31: ...njena kako bi osoblje imalo pristup elektri nim i mehani kim komponentama Svi priklju ci odvla iva a su dizajnirani prema standardnoj veli ini spiralnih cijevi Rotor Odvla iva je opremljen osu uju im...

Page 32: ...je slobodan H Spojite su a sa glavnim napajanjem okretanjem izolacijskog prekida a u polo aj ON ili alternativno spojite utika u uti nicu I Odaberite polo aj MAN na prekida u crnom su a a Postavite g...

Page 33: ...ra aju Promjenjeni volumen zraka Promjenjena temperatura regeneracijskog zraka Curenje zraka O istiti ili zamijeniti filter Provjeriti osigura e Provjeriti otvore i prigu nice Provjeriti napetost reme...

Page 34: ...IP44 v detts gnek Burkolat A burkolat 2333 rozsdamentes ac lb l k sz lt A p r tlan t fels r sz ben lev levehet panel a szervizel k sz m ra hozz f rhet v teszi villamos s mechanikus r szeket A p r tlan...

Page 35: ...k zzel a ventil tor forg r sz t ellen rizve hogy az akad lymentesen forog F Ellen rizze hogy a nedves s a sz raz leveg zsalui nyitott ll sban vannak s a csatorn k nincsenek eldugulva G Ellen rizze hog...

Page 36: ...Nincs vagy korl tozott p r tlan t s A sz r eldugult A villamos f t egys g hib s Korl tozott leveg raml s A rotor nem forog Bels sziv rg s a berendez sben V ltoz leveg mennyis g V ltoz regener l h m r...

Page 37: ...ezione opposta all aria secca viene ridotta la percentuale d umidit del materiale del rotore L aria riattivante esce dall essicatore come aria calda e umida la quale dopo sar scaricata fuori dall edif...

Page 38: ...deumidificato possibile deumidificare tutto il locale o solo la parte danneggiata In quest ultima opzione viene applicata la piastra di materie plastiche l aria secca per viene fornita da sotto la pia...

Page 39: ...ito corto con l angolo di 90 gradi D Collegato solo lo scarico dell aria secca e umida E Tutti gli scarichi collegati Correzione K dB con la banda ISO nr Frequenza centrale Hz Percorso del rumore LWA...

Page 40: ...amintas i ner dijan io 2333 plieno Sausintuvo vir uje yra skydas kuris gali b ti nuimamas tam kad aptarnaujantis personalas gal t prieiti prie elektrini ir mechanini dali Visi sausintuvo ortaki sujung...

Page 41: ...ite kad jis sukasi be joki kli i F sitikinkite kad dr gno ir sauso oro sklend s yra atviros o ortakiai var s ir neu kim ti G sitikinkite kad elektros maitinimo saugiklis turi atitinkam tamp ir kad tai...

Page 42: ...s kambario s lygomis R 102 Sab 10 GEDIM PAIE KA Gedimas Galima problemos prie astis Taisymas Sausintuvas dirba nena iai U kim tas filtras Elektrinio ildytuvo gedimas Oro srauto jud jimas yra apribotas...

Page 43: ...as ir projekt ti spir les vadu standartiem izm riem Rotors Susin t js ir apg d ts ar susin anas rotoru ra otu no susin anas materi la Rotors ir apg d ts ar matrici no vi ot sk rda un plakana karstumiz...

Page 44: ...kontaktdak u pie elektr bas t kla I Izv l siet susin t ja p rsl dz ja melna MAN poz ciju Uzst diet galveno p rsl dz ju oran a uz ON poz cijas 3 4 sekundes laik P rbaudiet vai rotors kustos l ni vai v...

Page 45: ...gaisa str va Rotors nerot Iek ja s ce ier c Main ti gaisa daudzumi Main ta reaktiv anas temperat ra Gaisa aizpl ana Not riet vai mainiet filtrus P rbaudiet dro in t jus P rbaudiet caurumus un drosele...

Page 46: ...richting tot de droge lucht zal de vocht in het material van de rotor afnemen De reactiverende lucht zal de ontvochtiger verlaten als warme en vochtige lucht die vervolgens uit het gebouw zal worden g...

Page 47: ...nnen behandeld worden In geval van de tweede optie wordt ere en kunstmatige plaat gebruikt waarbij de droge lucht onder de plaat wordt geleverd In beide gevallen dient de natte lucht uit het gebouw te...

Page 48: ...ctie K dB bij band ISO nr middenfrequentie Hz Route van het lawaai LWA 1 64 2 125 3 250 4 500 5 1000 6 2000 7 4000 8 8000 A 65 26 14 10 10 9 3 9 15 B 66 22 11 6 10 10 3 9 15 C 67 27 12 7 7 10 3 8 14 D...

Page 49: ...for service av elektriske og mekaniske komponenter Alle slanger til avfukteren er designet for tilkobling til standardst rrelse kanalene Rotor Avfukteren har en t rking rotor fabrikkert fra et t rkem...

Page 50: ...type H Koble avfukteren til de viktigste str mforsyninger ved skru isolasjonsbryteren p ON eller alternativt koble st psel til stikkontakten I Velg MAN posisjon p operasjonsbryteren svart av avfuktere...

Page 51: ...avfukting kapasitet Tett filter Feil med elektrisk varmeapparat Redusert luftstr m Ingen rotasjon p rotor Intern lekkasje i enheten Forandret luftvolum Forandret reaktiveringstemperatur Luftlekkasje...

Page 52: ...wst pnie ogrzanego powietrza w dalszym ci gu wzrasta do oko o 100 C W momencie gdy powietrze reaktywacyjne przechodzi przez rotor w kierunku przeciwnym do powietrza suchego obni y si zawarto wilgoci w...

Page 53: ...a si przewod w z tworzywa sztucznego a nie przewod w spiralnych Metoda osuszania r ni si zale nie od sytuacji oraz od konstrukcji kt r nale y osuszy Osuszone mo e zosta ca e pomieszczenia lub jego zni...

Page 54: ...u pod k tem 90 stopni D Pod czony wy cznie wylot suchego i mokrego powietrza E Wszystkie wyloty pod czone Korekta K dB przy pa mie ISO nr Cz stotliwo rodkowa Hz Droga ha asu LWA 1 64 2 125 3 250 4 500...

Page 55: ...cat scade cantitatea de umiditate din materialul rotorului Aerul de reactivare p r se te dezumidificatorul ca i aer cald i umed care este ndep rtat ulterior din cl dire 4 DESCRIEREA PRODUSULUI Dezumid...

Page 56: ...ai partea avariat a acesteia n cazul celei de a doua op iuni de folosesc pl ci din maretial sintetic iar aerul uscat trece sub plac n ambele cazuri aerul umed trebuie transportat din cl dire printr un...

Page 57: ...tate Corectare K dB la o band ISO nr Frecven medie Hz Direc ie zgomot LWA 1 64 2 125 3 250 4 500 5 1000 6 2000 7 4000 8 8000 A 65 26 14 10 10 9 3 9 15 B 66 22 11 6 10 10 3 9 15 C 67 27 12 7 7 10 3 8 1...

Page 58: ...RU 1 DHA 160 DHA 250 15 2 DHA 160 DHA 250 100 30 C 40 C 3 3 30 C 40 C 100 C 4 44 2333 IP 54 ISO F 30 100...

Page 59: ...0 1 MAN AUTO 5 DHA 160 DHA 250 400 2 DHA 160 125 DHA 250 2x 80 DHA 250 6 A B OFF C D E F G H ON I MAN ON 3 4 J K L DHA 250 6 M AUTO...

Page 60: ...ISO Hz LWA 1 64 2 125 3 250 4 500 5 1000 6 2000 7 4000 8 8000 A 65 26 14 10 10 9 3 9 15 B 66 22 11 6 10 10 3 9 15 C 67 27 12 7 7 10 3 8 14 D 67 27 13 7 10 10 3 8 14 E 59 24 10 11 6 4 5 14 20 LWA 10 1...

Page 61: ...10...

Page 62: ...kanalanslutningar r avsedda f r anslutning till spirokanaler av standarddimension Rotor Avfuktaren r utrustad med en torkrotor av adsorptionstyp Rotorn r uppbyggd av plana och wellade ark med kiselgel...

Page 63: ...mmande f rem l kvargl mda i avfuktaren D Kontrollera att installerade spj ll r ppna och att kanalerna r rena E Kontrollera att filtret sitter p plats F Kontrollera att s kringarna r hela G Kontrollera...

Page 64: ...fektniv i dB A rel 10 12 W LWAO Ljudeffektniv i oktavband dB A rel 10 12 W K Korrektion f r ber kning av LWAO LWAO LWA K dB A Ljudeffektniv vid rumsekvivalent R 102 Sab 10 FELS KNINGSSCHEMA SYMPTOM T...

Page 65: ...ablov su ilnika imajo standardne dimenzije za spiralne kable Rotor Su ilnik je opremljen s su ilnim rotorjem iz su ilnega materiala Rotor ima matico iz valovite plo evine in ravne plo evine na kateri...

Page 66: ...prosta H Priklju ite su ilnik na glavni elektri ni priklju ek tako da nastavite izolacijsko stikalo v polo aj ON oziroma da vtaknete vti v vti nico I rno stikalo su ilnika nastavite v polo aj MAN Nast...

Page 67: ...enja Zama en filter Okvara elektri nega grelnika Omejen pretok zraka Rotor se ne obra a Notranje pu anje v napravi Spremenjene koli ine zraka Spremenjena temperatura reaktivacije Pu anje zraka O isti...

Page 68: ...a rotor ako tepl vlhk vzduch ktor sa n sledne odv dza z budovy 4 OPIS V ROBKU Su i bol naprojektovan tak aby sp al po iadavky IEC pre ochrann stupe OP 44 Kryt Kryt je vykonan z nehrdzavej cej ocele 2...

Page 69: ...nej asti su i a do polohy OFF C Otvorte servisn panel na hornej strane su i a a uistite sa e v zariaden a v elektrickej asti nezostali cudzie predmety D Uistite sa e je nain talovan filter vzduchu E R...

Page 70: ...luku v okt vovom p sme dB A rel 10 12 W K Oprava v po tu LWAO LWAO LWA K dB A rove sily hluku v izbov ch podmienkach R 10 2 Sab 10 ODSTRA OVANIE POR CH Porucha Mo n pr ina probl mu N pravn innosti iad...

Page 71: ...UA 1 DHA 160 DHA 250 15 2 DHA 160 DHA 250 30 C 40 C 3 3 30 C 40 C 100 C 4 44 2333 54 ISO F 30 100 0 1 MAN AUTO...

Page 72: ...5 DHA 160 DHA 250 400 2 DHA 160 125 DHA 250 2x 80 DHA 250 6 A B OFF C D E F G H ON I MAN ON 3 4 J K L DH 250 6A M AUTO 7 15 off...

Page 73: ...r LWA 1 64 2 125 3 250 4 500 5 1000 6 2000 7 4000 8 8000 A 65 26 14 10 10 9 3 9 15 B 66 22 11 6 10 10 3 9 15 C 67 27 12 7 7 10 3 8 14 D 67 27 13 7 10 10 3 8 14 E 59 24 10 11 6 4 5 14 20 Symbols LWA A...

Page 74: ...10...

Page 75: ...Name Component S1 S2 On Off Man Auto switch h Runtime meter HS Humidistat A Amperemeter P1 Terminal block 7 pin E React heater M1 Drive motor rotor C Capacitor P2 Terminal block 4 pin P3 Terminal for...

Page 76: ...Name Component S1 S2 On Off Man Auto switch h Runtime meter HS Humidistat A Amperemeter P1 Terminal block 7 pin E React heater M1 Drive motor rotor C Capacitor P2 Terminal block 4 pin P3 Terminal for...

Page 77: ...r ces NL wij verklaren dat de toestellen NO vi erkl rer at innretninger PL deklarujemy e urz dzenia RO declar m c dispozitivul este conform cu RU SE vi f rs krar att apparater SI izjavljamo da je opre...

Page 78: ...riales y components de alta calidad que pueden ser reciclados y reutilizados Cuando vea este s mbolo de una papelera con ruedas tachada junto a un producto esto signifi ca que el producto est bajo la...

Page 79: ...ukt jest oznaczony powy szym symbolem przekre lonego kosza na miecie oznacza to e produkt spe nia wymagania Dyrektywy Europejskiej 2002 96 EC Zaleca si zapoznanie z lokalnym systemem odbioru produkt w...

Page 80: ...DESA Poland Sp z o o ul Magazynowa 5a 62 023 G dki Poland www desapoland pl DESA Italia SRL Via Tione 12 Pastrengo Verona VR Italy 37010 www desaitalia com...

Reviews: