Model: MC-1-DE
Doc Ref. No:-m05dom102
Issue No:-00
Page 13 of 76
User’s Manual
Mode: Server
Time format: UTC
Network Interface: 10/100 Mbps
Interface: RJ-45 Connector (Front Panel)
Additional Event Outputs
Two independent configurable Event outputs
Configuration: Individual configurable time period and pulse ON time
through Serial Terminal
Time Period: 1 to 86400 seconds (24 Hr.) max
ON Time: min. 50 milliseconds and max 50% of period time set for particu-
lar event
Event contact capacity: 350 VDC, 120mA maximum
Interface: 4-Way Terminal Strip (Front Panel)
INTERFACE
Status LED
Power
: Red
1 PPS
: Red
Watchdog
: Red
GPS Locked : Green(GPS LOCK)
TX : Red (Available only when serial output is available)
RX :Red (Available only when serial output is available)
Programming
Using HyperTerminal in a local PC via serial terminal.
Programmable parameters:
Global Time zone correction
Serial data format selection (NGTS or T-FORMAT or NMEA)
Password Protection
Network Settings:
IP address, Subnet mask, Gateway and SNMP Manager IP addresses
configurable through Telnet remote login.
All network configurations are password protected.
POWER SUPPLY
AC: 85 to 264 V, 47-440 Hz
DC: 125-300 V
Power Consumption: <10W Typical (40W Max)
Compliance
:
EN55011(CISPR11), EN55022 (CISPR22) Class B
OPTIONAL
POWER SUPPLY
DC: 18 – 75 V
Power Consumption: 10W Max
PHYSICAL DIMEN-
SIONS
Width: 143mm
Depth: 140 mm
Height: 72mm
Weight: 0.9 Kg(Approx)