13. Ethernet Communications: Telnet, SNMP
13.1 Telnet
After network connection established the GPS Master Clock model MC-1-M can be configure remotely
from a work station using command line interface (Telnet). Telnet configuration GPS Master Clock model
MC-1-M is password protected. GPS Master Clock model MC-1-M model several parameters can
configure using Telnet are shown in Table. To setup a Telnet connection please refers Appendix. model
MC-1-M supports only one Telnet session at a time. If the system is not disconnected properly then
Telnet session will be timed out and disconnected after 10 minutes.
Command
Description
Reference
H
Command list supported by model MC-1-M Model
Appendix E
Appendix E
CC
To view Current Configuration of model MC-1-M model.
IP
Sets the network IP address, Ethernet port, of model MC-1-M. After this
command connection to Telnet prompt will be lost and user needs to
reopen Telnet prompt. Factory set value is : 192.168.100.153
MASK
Sets the Network IP mask address, Ethernet port, of model MC-1-M.
Factory set Value is : 255.255.255.0
GTY
Sets the Network IP Gateway (factory set route address), Ethernet port, of
model MC-1-M.
Factory set Value is : 192.168.100.254
SIP1
Sets the IP address of SNMP manager which should receive any Trap
massages generated by model MC-1-M Agent.
Factory set value is 192.168.100.73
SIP2
Sets the IP address of SNMP manager which should receive any Trap
massages generated by model MC-1-M Agent.
Factory set value is 192.168.100.73
SRC
Sets the SNMP Read Community. The input could be any ascii string with
1-20 characters. Factory set value is: masibus
For detail of Read Community refer section: 12.2.2
SWC
Sets the SNMP Write Community, factory set value is masibus. The input
could be any ascii string with 1-20 characters.
For detail of Write Community refer section: 12.2.2
STRT
Used to modify stratum of model MC-1-M when it is not synchronized.
Factory set value is 1. For detail about stratum refer Section 11.3.2.
U
Sets the User name Telnet session, current Ethernet port, of model MC-1-
M.
Factory set Value is masibus (case sensitive).
P
Sets the Password Telnet session, current Ethernet port, of model MC-1-M.
Factory set Value is masibus (Case Sensitive).
IRIG
Used to configure UTC/Local time on IRIG output port.
Factory set Value is No – Transmit local time on IRIG-B Port.
I_1344
Used to configure IEEE-1344 C37.118-2005 protocol on IRIG-B output port.
Factory set Value is No-Disable IEEE 1344.
For detail about IEEE 1344 refer section: 10.2.2.4
Q
Quit the telnet configuration
Table 13.1: Configurable Parameters through Telnet
NOTE: 1) NTP output stops during Telnet session in progress.