Model: MC-1-M (2U)
Doc. Ref. no. : m05/om/101
Issue no. 14
User’s Manual
Page 48 of 103
NOTE:
1. The unit will enter the configuration as soon as it will receive CONFIG command followed by an
“Enter”.
2. Once the configuration mode is entered, the unit will stop sending time frames on COM2.
3. If user hits “Enter” key of PC keyboard without giving any command, unit will come out of
configuration mode and the time frames will start getting transmitted from COM2 again.
4. In case of improper entry of command, following message will appear on the screen:
----------------------------------------------------------------------------------------------
INVALID COMMAND
ENTER COMMAND TO CONFIGURE PARAMETER
TO CONTINUE PRESS ENTER
10.2 Configuration Commands
GPS Master Clock Model MC-1-M COM2 terminal can be used for configuring communication parameters
of serial port settings for COM2 terminal, output time string format (T-format / NGTS) on COM2 terminal ,
time display format, general parameters settings, time zone offset, password, standard and additional
event time outputs, antenna cable propagation delay, defaulting Ethernet port addresses.
All commands types are mentioned as subtitle name in below descriptions.
10.2.1 General Commands:
•
Command: CONFIG
This command lets the user to enter in the configuration mode. After giving command ‘CONFIG’ and
pressing Enter key, unit will stop the transmitting serial time output on COM2 and unit will ask the user to
enter the password on HyperTerminal, as shown below:
----------------------------------------------
T1101022120401
T1101022120501
CONFIG
ENTER PASSWORD :
----------------------------------------------
•
Message: ENTER PASSWORD
There are two passwords for GPS Master Clock Model MC-1-M. One is user-defined password, which
can be changed by the user through password configuration command and other is master password
which cannot be configured or visualize in menu settings. User defined password factory set is
‘MASIBUS’. If user changes the user password by configuration command, user has to enter new
password instead of factory set password.
If user changes the user password by configuration command, factory set password will change from
‘MASIBUS’ to the new password entered. User has to remember if the new password is configured by
user as there is no option to read the set password.