Model: MC-1-M (2U)
Doc. Ref. no. : - m05/om/101
Issue no. 14
Page 59 of 103
User’s Manual
10.2.10 Miscellaneous Command:
Other available commands are as follows:
•
Command: D
Description: This command sets following parameters of GPS Master Clock Model MC-1-M to their
default Value.
Keypad Parameter
Command
Value
Meaning
SET HOUR MODE
STx
2
24 Hour Mode
SET BAUD RATE
SBx
96
9600 baud rate for COM2 terminal
SET PARITY
SPx
0
NONE parity for COM2 terminal
SET STOP BIT
SSx
1
1 Stop Bit for COM2 terminal
SET TIME FORMAT
SUx
2
Local Time
SET TRANSMIT
MODE
TC2x
2
T-format frame on COM2 terminal
SET EVENT MODE
Ex
1
Event in per Minute Mode
ADD EVENT
ETx
60
ET1, ET2, ET3, ET4 event at 60 seconds
EVENT ON TIME
EWx
50
Pulse width ON time of 50 milliseconds for
all additional events
Table 10.2: Default Command parameters
If user enters the default command in GPS Master Clock Model MC-1-M, then the COM2 serial terminal
communication parameters gets default as per above table. User has to set the PC Serial terminal
communication parameters to mentioned default values in order to continue with configuration mode on
COM2 terminal.
•
The above settings are defaulted with the DEFAULT menu in keypad
menu section. If user defaults GPS Master Clock Model MC-1-M settings
using keypad menu, user should take care of all outputs affected due to
default i.e. time & date on GPS display, events connected to peripheral
devices, time frame coming on COM2 terminal of GPS Master Clock
Model MC-1-M device.
•
This default command does not affect the NTP Ports IP address
configuration, SPD value, Manual time.
•
Command: R
This command will reset GPS Master Clock Model MC-1-M.
This command will reset GPS Master Clock Model MC-1-M unit. As a result of
which, all the outputs will be stopped or there will be change in relay and
pulse output till unit boots up again.