RS-232C INTERFACE - Section 7
MTS-3000 SERIES OPERATION AND REFERENCE MANUAL 7-7
CU M004 01A
###########
0$17$
#
7(67
#
6<67(06
AIC# Amplitude Ic
•
Sets the amplitude of Ic for the currently selected fault state.
•
Valid values are 0 - 25.00 (amps.)
AIS x y z Amplitude Current Specified
•
Sets the specified channel(s), current amplitude, for the specified fault state
•
Where x = value of bit pattern of channels to be changed, Ia=1, Ib=2, Ic=4
•
Where y = current amplitude: 0 - 25.00 (amps)
•
Where z = fault state: 0 = present, 1 = prefault, 2 = fault
IMD# Current Mode
•
Set the Current Mode.
•
Valid values are 2, 3, 10, 11.
2 - HI current range (25A, 15V)
3 - Low current range (12A, 30V)
HIS x 2 y z p Set Percent Harmonic for specified current channels
•
Where x = value of bit pattern of channels to be changed, Ia=1, Ib=2, Ic=4
•
Where y = harmonic #, valid values are 2 - 10
•
Where z = percent harmonic
,
valid values are 0 - 50.0 (%)
•
Where p = phase of harmonic relative to harmonic, valid values are 0 - 360
7.2.6 Phase Control
These phase commands set the phase angle of the voltage and current.
7.2.6.1 COMMANDS.
Command Description
PIS x y z Phase angle of specified current channel
•
Sets the specified current channel(s), phase angle for the specified fault state
•
Where x = value of bit pattern of channels to be changed, Ia=1, Ib=2, Ic=4
•
Where y = phase angle: -360 to 360.0 (degrees)
•
Where z = fault state: 0 = present, 1 = prefault, 2 = fault
PVS x y z Phase angle of specified voltage channel
•
Sets the specified voltage channel(s), phase angle for the specified fault state
•
Where x = value of bit patern of channels to be changed, Va=1, Vb=2, Vc=4
•
Where y = phase angle: -360 to 360.0 (degrees)
•
Where z = fault state: 0 = present, 1 = prefault, 2 = fault