SPECIFICATIONS - Section 2
MTS-3000 OPERATION AND REFERENCE MANUAL 2-3
CU M004 01A
0$17$
#
7(67
#
6<67(06
2.3 METERING
2.3.1 Time measurement
Measures interval from either fault initiation or an external start trigger signal
0 - 99999 sec, auto-ranging scale
0 - 99999 cycles, auto-ranging scale
Resolution: 0.1 ms/ 0.1 cyclesAccuracy: ± 0.5ms, ± 1 digit
Two wire pulse timing mode
2.3.2 Frequency measurement
Resolution, 8Hz - 99.999Hz: ± 0.001 HzAccuracy: ± 0.01 Hz
Resolution, 100Hz - 499.99Hz: ± 0.01 Hz Accuracy: ± 0.05 Hz
Resolution, 500Hz - 1000.0Hz: ± 0.1 Hz Accuracy: ± 0.1 Hz
2.4 STATIC/DYNAMIC TESTING CAPABILITIES
Phase to ground, phase to phase and three phase faults (when equipped with sufficient modules)
Phase, frequency, voltage and current ramping with adjustable ramp rates
Programmable auto-reclose time delay and reclose-into-fault events
Programmable breaker opening and closing times
Fault incidence angle control (point-on-wave)
2.5 OPTIONS
Control Module Options:
Option 01
MTS-3010 Programmable Digital I/O Module with trigger channels.
Option 02
DC Current Source. Option 01 must be present.
Maximum configuration: one per Control Module, two if there’s no DC Voltage Module.
Option 03
Digital I/O Expansion. Option 01 must be present (Future).
Option 04
MTS-3020 DC Voltage Module.
Maximum configuration: one per Control Module.
Option 05
240V, 50/60 Hz line input Control Module.
2.5.1 System Options
Option 18
Digital I/O and DC Voltage Test Lead Kit
Option 19
Additional Operation and Reference Manual
Option 20
Additional One Year extended warranty
2.5.2 AC Voltage Module Options
Option 41
240V, 50/60 Hz line input
Option 42
2nd AC Voltage Channel
Option 43
3rd AC Voltage Channel
Option 44
AC Voltage Test Lead Kit
Maximum configuration: three Channels per ACV Module, two Modules per stack