
OPERATION SUMMARY - Section 3
3-16 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL
#
0$17$
#
7(67
#
6<67(06
###########################################
CU M004 01A
4.
Incremental changes to the setting can be made with the MODIFY rotary knob. When finished, disable
Modify by pressing SET again. This will extinguish the SET LED and the F1 LED, and restore
previously existing readings to the CONTROL display.
5. To apply the DC voltage to a connected load, press the ON switch on the DC VOLTS module. This
connects the programmed DC to the output terminals and lights the ON LED status indicator,
regardless of the status of the AC outputs.
3.3.4.2 ADVANCED DC VOLTAGE OUTPUT.
Advanced dc voltage mode allows the user to set different DC voltage levels for each of the prefault, fault,
and postfault states.
1. Press SET on the DC VOLTS module. The SET LED will turn on, and the display in the CONTROL
section of the CM will change, as shown.
2.
Press F2 on the CM to set enable fault state specific voltage levels
3. Select F1, F2, or F3 to program the Prefault, Fault, or Postfault levels respectively.
3.3.5 DC Current Output
This optional feature is for testing DC current operated targets on older electromechanical relays. These
targets are typically connected in series with the relay trip output contact so the MTS contact sensing
INPUT 1 is used to supply DC current to the external relay output circuit.
NOTE: The low impedance nature of this source could provide the necessary trip path to inadvertently trip
an auxillary relay or circuit breaker. The DC current output only should be used when the
protective relays trip output circuit is properly isolated.
FIGURE 3.12
DC CURRENT ADJUST