© 2010 Magnum Energy, Inc.
24
3.0 Setup
03D AGS Temp
,
04E Gen Run Temp
, and
01 Temperatures
under the
TECH button.
Default setting
-
Fahrenheit
01E Viewing Ports:
The
Viewing Ports
menu item sets the main screen
to either automatically scroll through each connected port, or requires you
to manually select each port by pressing the PORT button. Adjusting the
seconds allows you to select how long the Port screen is displayed before
it automatically scrolls to the next screen. Range is
off-60 seconds
.
Default setting
-
Auto Roll (sec) = off
01F Aux Relay State:
Selections are
Open
,
Auto
, and
Close
.
Open
- Manually opens the Aux Relay contacts. This setting manually
controls the device connected to the Aux Relay, or tests the Aux Relay
operation.
Auto
- Uses the
Relay Close
and
Relay Open
settings from the
01G Aux
Relay V Trip
menu, and the
Close Delay
and
Open Delay
settings in the
01H Aux Relay Timing
menu to automatically control the Aux Relay.
Closed
- Manually closes the Aux Relay. This setting manually controls the
device connected to the Aux Relay, or tests the Aux Relay operation.
Default setting -
Open
Info:
When the open or closed selections are made, the Aux
Relay will open or close without any time delay.
01G Aux Relay V Trip:
This menu sets the Battery Voltage Trip point to
open and close the Aux Relay contacts. Once the battery voltage reaches
the trip point, the relay will open or close once the time set in the
01H
Aux Relay Timing
menu item is satisfied.
Relay Close
- Set this voltage to
close the Aux Relay contacts. This range
can be below or above the
Relay Open
setting depending on if you want
the Aux Relay to be
Active Low
or
Active High
.
Range is
8-17
(12 VDC),
16-34
(24 VDC) and
32-51
(48 VDC)
Relay Open
- Set this voltage to open the Aux Relay contacts. This range
can be below or above the
Relay Close
setting depending on if you want
the Aux Relay to be
Active Low
or
Active High
.
Range is
8-17
(12 VDC),
16-34
(24 VDC) and
32-51
(48 VDC)
Default settings
-
For both the
Relay Open
and
Relay Close
settings:
14
(12 VDC),
28
(24 VDC) and
56
(48 VDC).
Example - Active Low:
Set the
Relay Close
voltage below the
Relay
Open
voltage. If the
Relay Close
voltage is set at 12.0 VDC and the
Relay Open
voltage is set at 14.5 VDC, the relay would close when
the battery voltage dropped to 12.0 VDC and open when the battery
voltage rises to 14.5 VDC. This configuration might be used to control
a battery exhaust fan or as a simple PV charge controller.
Example - Active High:
Set the
Relay Open
voltage below the
Relay
Close
voltage. If the
Relay Open
voltage is set at 12.0 VDC and the
Relay Close
voltage is set at 14.5 VDC, the relay would open when
the battery voltage dropped to 12.0 VDC and close when the battery
voltage rises to 14.5 VDC. This configuration might be used to control
a low voltage disconnect circuit for a DC load.
•
•
•