9.0 Using the ME-ARC Remote
© 2012 Magnum Energy, Inc.
40
AGS Menu
(Button: Menu)
AGS Menu
Selections/Adjustments
Inverter
Level
ME-AGS-N
Required
ME-ARC
Required
CTRL: 03 Gen
Control
OFF, ON, AUTO, Test
Level 1
Rev 5.0
Rev 2.0
OFF, ON, AUTO
Level 1
Rev 5.0
Rev 2.1
METER: 03 AGS Meters
03A AGS Status (Read Only)
Level 1
Rev 5.0
Rev 2.0
03B DC Volts - AGS (Read Only)
Level 1
Rev 5.0
Rev 2.0
03C Gen Run Time (Read Only)
Level 1
Rev 5.2
Rev 2.0
03D AGS Temp (Read Only)
Level 1
Rev 5.0
Rev 2.0
03E Since Gen Run (Read Only)
Level 1
Rev 5.0
Rev 2.0
SETUP: 04 AGS Setup
04A Gen Run
VDC
Start = OFF, 9.0-16.0
(12V), 18.0-32.0 (24V),
36.0-64.0 (48V) VDC
Level 1
Rev 5.0
Rev 2.0
Stop = OFF, 9.0-16.0
(12V), 18.0-32.0 (24V),
36.0-64.0 (48V) VDC,
Float
Start/Stop Delay = 0-127
sec., 1-127 min.
Table 9-2, Software Differences Between ME-ARC Revisions
Autostart Condition
Autostop Condition
See SETUP Menu
Page
Starts on low battery
voltage (DC voltage con-
nected to Terminals #3
and #4)
Stops on higher battery
voltage
04A Gen Run VDC
42
Stops at Float charge
after a set time period
(using Absorb Done
Time setting)
04A Gen Run VDC
(Set Stop Gen Volts
= Float)
42
Stops at Float charge
after battery current re-
quirement is low (using
Absorb Done Amps)
04A Gen Run VDC
(Set Stop Gen Volts
= Float)
42
Stops at Float charge
using a battery SOC set-
ting (using Absorb Done
SOC setting)
²
04A Gen Run VDC
(Set Stop Gen Volts
= Float)
42
Starts at a set time daily
Stops at a different set
time daily
04B Gen Run Time
44
Starts on high AC amps
to an inverter load
¹
Stops on lower AC amps
to an inverter load
¹
04C Gen Run Amps
44
Starts when the battery
SOC
²
is low
Stops when the battery
SOC
²
is higher
04D Gen Run SOC
45
Starts when tempera-
ture increases
Stops after a set time
period
04E Gen Run Temp
46
Table 9-1, ME-ARC Autostart/Autostop Matrix
Note
¹
:
Only applicable to MS-PAE and MS-PE inverters.
Note
²
:
Autostart/stop conditions using SOC require the ME-BMK (Battery Monitor).