12.0 ME-AGS-N Remote Troubleshooting
If using
SETUP: 04B Gen Run Time
, con
rm you have not set
the total run time (start time to the stop time) longer than the
SETUP: 04F Max Gen Run Time
setting.
If using
SETUP: 04C Gen Run Amps
, con
rm the inverter load(s)
that is used to determine the
Stop Gen AC Amps
setting is not
required to run longer than the
SETUP: 04F Max Gen Run Time
setting.
If using
SETUP: 04D Gen Run SOC
, con
rm that the
METER: 04A
BMK SOC
reading is not
Thinkn
, but shows an actual percent-
age reading on the display (i.e.,
85%
), and the
Stop Gen SOC
setting can be satis
ed before the
SETUP: 04F Max Gen Run
Time
setting is reached.
If using
SETUP: 04E Gen Run Temp
, the temperature around
the remote temperature sensor has not reached the
Gen Run
Temp
setting. You need to either lower the
Gen Run Temp Start
setting, determine how to cool the area (remote temp sensor
location) to below the
Gen Run Temp Start
setting before the
04F Max Gen Run Time
setting is reached, or increase the
Max
Gen Run Time
setting.
Lastly, con
rm that your warm-up and/or cooldown time when added
to your autostop condition does not exceed the
SETUP: 04F Max Gen
Run Time
setting.
Info:
Beginning with Revision 5.2 of the ME-AGS-N, the
Max Gen Run
Time
setting can be defeated. In some cases, it may be appropriate
to set the
Max Gen Run Time
setting to
OFF
. However, this feature is
mainly provided as a safety feature to ensure the generator doesnt
run longer than the time it takes to reach the autostop conditions or
to expend the generators fuel capacity, whichever occurs
rst take
this into consideration if this setting is defeated.
• Gen Run Fault
The generator successfully started and ran for more
than two minutes, but the generator unexpectedly stopped by itself be-
fore the active AGS autostop condition was
nished.
Info:
The AGS module determines the generator is running by moni-
toring the gen run sense voltage/signal. When this gen run sense
voltage/signal is no longer available, the AGS thinks the gen is off
or has stopped.
Info:
Gen run fault detection is not active if the generator is manu-
ally started.
Remedy:
A) If the generator is still running: Con
rm you are getting the cor-
rect gen run sense signal to the AGS module. For assistance, refer to
Section 6.2 Generator Starting/Running Troubleshooting.
B) If the generator is not running: Check the generator for fault
codes and adequate fuel. If neither is an issue, check the genera-
tors owners manual for troubleshooting tips to determine why it
may have shut down on its own.