8.0 Using the ME-RC Remote
© 2012 Magnum Energy, Inc.
28
8.0 Using the ME-RC Remote
The ME-RC remotes AGS menus under the AGS and TECH buttons allow
you to customize and monitor the operating parameters for your autostart/
autostop generator system. To help con
gure and operate the AGS with your
ME-RC, refer to the mini index below to direct you to the appropriate section.
8.1 ME-AGS-N Setup using the ME-RC
page 28
8.2 ME-AGS-N Functional Testing using the ME-RC
page 33
8.3 ME-AGS-N Operation/Monitoring using the ME-RC
page 34
8.4 Enabling the ME-AGS-N using the ME-RC
page 36
8.5 Starting and Stopping the Generator using the ME-RC
page 36
8.6 ME-AGS-N Menu Map using ME-RC
page 37
Figure 8-1, ME-RC’s AGS Confi guration Access Buttons
DC 12.6V 5A
Status...
01 AGS Control
SHORE AGS METER SETUP TECH
AGS and TECH Buttons
8.1 ME-AGS-N Setup using the ME-RC
Press the AGS button on ME-RC remote (Figure 8-1), and then rotate the
SELECT knob to navigate to the AGS menus. These menus allow the genera-
tor to be automatically started and stopped based on different parameters.
Using Table 8-1, determine the speci
c autostart and autostop condition with
which you want the generator to be automatically controlled, and then use
that speci
c menu setting to con
gure the AGS.
Note:
For information on using the
AGS: 01 AGS Control, AGS: 02 AGS Sta-
tus,
and
AGS: 08 AGS TECH
menus, refer to Section 8.3 ME-AGS-N Opera-
tion/Monitoring using the ME-RC.
This AGS manual covers ME-RC remote controls with a revision of 1.5 to
2.612. There may be differences between revisions that affect your AGS
setup/operation. Use Table 8-2 to familiarize yourself with the differences
between AGS revisions.
Info:
Refer to your ME-RC owners manual to determine your remotes
revision (or see the
AGS: 08 AGS TECH
menu section on page 35).
Table 8-1, ME-RC Autostart/Autostop Matrix
Autostart
Condition
See AGS
Menu
Page
Autostop
Condition
See AGS
Menu
Page
Gen starts on high
temperature
04 Start
Temp F
30
Gen stops
after a set
time period
03 Run
Time Hour
30
Gen starts on low
inverter battery
voltage
05 Start
Volts
32