9.0 Using the ME-ARC Remote
• Set Start Gen AC Amps
This setting determines when the generator
would start depending on the AC amps level of the load the inverter is
running. In order for the generator to autostart, the loads amps level
must be maintained continuously above the
Start Gen AC Amps
setting
for the duration of the
Start Amps Delay
setting.
Default setting:
Set Start Gen AC Amps = OFF
Range:
OFF, 5 - 60 Amps
• Set Start Amps Delay
This setting determines the amount of time
that the inverter loads current must continuously remain above the
Start Gen AC Amps
setting for the AGS to initiate an autostart.
Default setting:
Set Start Amps Delay = 120 Seconds
Range:
0 - 127 Seconds, 1 - 127 Minutes
• Set Stop Gen AC Amps
This setting determines when the generator
would stop depending on the drop in the AC amps needed for the load
the inverter is running. In order for the generator to autostop, the load
amps level must drop continuously below the
Stop Gen AC Amps
setting
for the duration of the
Stop Amps Delay
time setting.
Default setting:
Set Stop Gen AC Amps = 20 Amps
Range:
5-59 Amps
• Set Stop Amps Delay
This setting determines the amount of time
that the AC load must be continuously smaller than the
Stop Gen AC
Amps
setting before the generator automatically stops.
Default setting:
Set Stop Amps Delay = 120 Seconds
Range:
0 - 127 Seconds, 1 - 127 Minutes
Where should I set Gen Run Amps?
Typically, the generator should start
when the AC load amps is >70-75% of the inverter AC current output rat-
ing
¹
. This keeps the inverter from running too large a load and also keeps
the batteries from cycling unnecessarily. Set
Stop Gen AC Amps
just below
the start amps to ensure the large load has turned off. Set the start delay
time so surge loads dont trigger a false start, and the stop delay time is long
enough to ensure the load has turned off.
Amps Start/Stop Example:
In this scenario, most AC loads typically do
not exceed 20A when in Inverter mode. When a freezer or well pump starts,
the load exceeds 30A so the battery voltage starts to drop quickly. Instead
of cycling the batteries to a low voltage, set
Start Gen AC Amps
to
25A
with
a
60
-second delay (using
Set Start Amps Delay
menu). Set the
Stop Gen
AC Amps
menu to
20A
with a
60
-second delay (using
Set Stop Amps Delay
menu). After 60 seconds of detecting a larger than 25A load on the inverter,
the generator autostarts and powers the loads and recharges the batteries.
Once the AC amps load drops below 20A for 60 seconds, the gen will turn off.
SETUP: 04D Gen Run SOC Menu
Info:
This feature requires the optional ME-BMK (Battery Monitor
Kit). Refer to your ME-BMK owners manual to operate.
This menu starts and stops the generator based on the SOC (State of Charge)
reading from the attached battery monitor (see ME-BMK owners manual) as
shown on the METER buttons
04A BMK SOC
display. This is considered the
Note
¹
For a 4000 watt inverter, this means setting Start Gen AC Amps
at 25A.