Occupant Sensor Wiring
R
GRAFIK Eye
®
QS System Installation and Operation Guide 4
1234
1: COM
2: 24 V
3: MUX
4: MUX
12
ABC
Note: Use appropriate wire connecting devices as
specified by local codes.
Occupant
sensor
1 2 3 4 5 6 L N
Distribution Panel
L N
To Load 1
To Load 2
To Load 3
To Load 4
To Load 5
To Load 6
Control Wiring
Wiring the GRAFIK Eye
®
QS System
Class 2 / PELV USA Cable
IR Wiring
From external
IR connection
(by others)
Common and power (terminals 1 and 2):
Two 1,0 mm
2
(#18 AWG) each terminal
1,0 mm
2
(#18 AWG)
each terminal
2,5 mm
2
(#12 AWG)
each terminal
1234
12
ABC
1 2 3 4 5 6 L N
1,0 mm
2
(#18 AWG)
each terminal
230 V
1: IR DATA
2: IR COM
A: OCC SIG
B: 24 V
C: OCC COM
To control stations,
window treatments, or
other
GRAFIK Eye
QS
control units
Line Voltage/Mains Cables
and Load Wiring
Data (terminals 3 and 4):
Twisted, shielded pair 1,0 mm
2
(#22 AWG)
each terminal