Set Minimum Level (optional)
Some local regulations specify a
minimum lighting level for dimming
zones in occupied buildings. If this
pertains to you, follow these steps to
set up your minimum lighting level.
1. Enter programming mode (see page 12)
and select “Zone setup,” then “Min
level”. Press the OK button to accept.
2. Use the master buttons to highlight
“OFF” if you want your lights to go all
the way off at their minimum light level,
or “10%” if you want that to be the
minimum light level. Press the OK button
to accept.
Note:
Non-dim loads
will
turn off
regardless of the minimum level setting.
3. The info screen will display a
confirmation screen that your minimum
level has been saved.
4. Exit programming mode (see page 12).
R
GRAFIK Eye
®
QS System Installation and Operation Guide 9
Zone Setup
Set High End or Low End
High and low end trim settings limit the
maximum and minimum output of a
dimming zone. Trim levels are set
automatically when the load type is
programmed. Change the high or low
end trim for a zone only if the default
setting needs to be adjusted.
1. Enter programming mode (see page 12).
2. Use the master buttons to highlight “Zone
setup” and press the OK button to
accept.
3. Use the master buttons to highlight “High
end” or “Low end” (this example shows
low end). Press the OK button to accept.
4. Use the zone raise/lower buttons to set
the high end or low end trim for that
zone.
The info screen will display each zone
number and percentage as you adjust it.
Press the OK button to accept.
5. The info screen will display a
confirmation screen that your setting has
been saved.
6. Exit programming mode (see page 12).
Main menu
Occ sensor
Zone setup
Zone setup
High end
Low end
Set trim using
zone controls
Zone 2
Low end
OK
1
2
3
4
5
6
Use the
zone
raise/lower
buttons to
set the high
end or low
end trim for
that zone.
Master
buttons
OK
button
10%
Min level
OFF
Zone setup
Low end
Min level
Saved
Saved
Saved
Saved