GRAFIK Eye
®
QS Control Unit Installation and Operation Guide 24
Contact Closure Input (CCI) Setup
(wired directly to the GRAFIK Eye
®
QS control unit)
The integral contact closure input (CCI) on the back of the GRAFIK Eye
®
QS control unit
can be configured as:
Occupancy (default): Allows a wired occupancy sensor to be included in the list of
available sensors when setting up occupancy actions.
Emergency: This setting allows the GRAFIK Eye
®
QS control unit to work with a
LUT-ELI-3PH emergency lighting interface. When an emergency situation is detected,
all lights will go to full on, and will not change until the emergency signal is cleared.
Afterhours: Allows the CCI to start and end Afterhours.
Timeclock: Allows the CCI to enable and disable the timeclock.
Lockout: Prevents the user from making any changes to the control unit. The current scene will stay on until the CCI
enables normal operation.
Never Save:
Prevents any changes from being saved while the CCI is being used.
Disable CCI: The CCI will have no effect on the system and will not appear on the list of available occupancy sensors
within the sensor setup menu.
Changing the operation of the contact closure input:
1. Enter programming mode.
2. Use the Master buttons to highlight “CCI Setup” and press the OK button to accept.
3. Use the Master buttons to highlight “CCI Mode” and press the OK button to accept.
4. Use the Master buttons to highlight the mode you wish the CCI to control. Press the OK button to
accept.
5. The info screen will confirm that your setting has been saved.
6. Exit programming mode.
CCI Mode
Occupancy
Saved
Saved
Main menu
Save Mode
CCI menu
CCI Type
CCI Setup
CCI Mode
OK
Master
buttons
OK
button
Timeclock
(back) button
(continued on the next page)