60
EcoSystem
®
Programmer
Addressing New Ballasts
If new ballasts are added to an existing system, the ballasts must be
addressed using the EcoSystem programmer. This enables the
programmer to communicate with the ballasts and program their
settings.
NOTES:
To address all ballasts (for example, when a new system is installed),
refer to page 12.
To address a replacement ballast, refer to page 58.
1
1 From the Main Menu, tap
S
Syys
stte
em
m and then A
Ad
dd
drre
es
ss
s
N
Ne
ew
w B
Ba
alllla
as
stts
s..
2
2 Tap A
Ad
dd
drre
es
ss
s N
Ne
ew
w B
Ba
alllla
as
stts
s.
3
3 Read the instructions, then
tap
to continue.
4
4 Confirm that ballasts are
powered, then point the
programmer at any IR control
device and tap
to begin
addressing.
5
5 If all fixtures flash, tap
.
Fixtures will go to minimum
brightness as they are
addressed.
6
6 If all fixtures are at minimum
level, tap
.
C
Ca
au
uttiio
on
n!!
Do not tap
until all
fixtures flash and are at their
minimum level.
7
7 If all fixtures go to their high
level, tap
.
2
2
5