36
EcoSystem
®
Programmer
Limiting Restrikes
When there is a problem with the lamp, wiring, or ballast, the ballast
may continue to attempt to strike the lamp. Since this may be
undesirable, you can limit the number of restrikes to three times. If
the lamp still does not light, the ballast will not retry until instructed
to turn the lights off and back on again by a sensor or other system
input.
1
1 From the Configure Menu, tap
M
MO
OR
RE
E O
OP
PT
TIIO
ON
NS
S then L
Liim
miitt
R
Re
es
sttrriik
ke
es
s.
NOTE: For procedures on how to
select one or all ballasts and then
display the Configure menu, refer
to page 28.
2
2 Tap
to begin setup.
3
3 If selected ballasts flash and
go to their high level, tap
.
4
4 Select E
En
na
ab
blle
e to limit ballast
restrike attempts, or D
Diis
sa
ab
blle
e to
restore the default operation of
unlimited restrike attempts.
5
5 Depending on what you want
to do next, select:
• Continue Configuration of
Current Ballast(s)
• Configure Different
Ballast(s)
• Done
6
6 When done, if the last
configured ballast(s) flash and
go to their high level, tap
.
4
4
1
1