Engineering Guide CDA3000
3 Selection of inverter module
Forming of the DC-link capacitors
To form the DC-link capacitors the inverter modules must be connected to
the mains power at 400/460 V (CDA34.xxx) approx. every 6 months for
1 hour. The time is dependent on the storage temperature: Inverter
modules stored at approx. 45 °C only need be connected to the mains
approx. every 8 months.
Figure 3.4
Inverter module rating plate with year and month identification
Attention: If the inverters have been left standing for more than
8 months after shipping (see rating plate) the DC-link
capacitors must be reformed. This can be avoided if the
inverters are connected to the mains for one hour
approx. every 6 months.