Engineering Guide CDA3000
5-7
5 Communication and user modules
DE
EN
1
2
3
4
5
6
7
A
Figure 5.5
Interconnection of Lust drive units on the CAN bus
1
Control
2
Connection of 24 V supply voltage
3
Bus termination plug with resistor 120
Ω
4
Lust system bus cable type I or self-defined cable
Cable type for self-assembly
If the supplied cables are not of the required length, it is also possible to
make your own cables (1:1 connection). This relates to LS-BUS cable
type I.
Voltage supply, CAN bus
Voltage
24 V +20%
Voltage ripple
3 Vss
Current
100 mA per station
Table 5.4
Voltage supply
Cable type
Shielded with at least nine wires
Wires
Twisted-pair, 0.25 mm
2
Surge impedance
120
Ω
Length
Any, total distance must not exceed 80 mm
Table 5.5
Cable type
- +
24VDC
24 VDC
- - -
+
+
+
+
+
+
+
+
PLC