Powering and Initial Circuit Pack Installation for
Metropolis
®
DMXtend Shelf Horizontal Bay Mount
Initial Circuit Pack Installation
...........................................................................................................................................................................................................................................................
2 - 2 1
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
LNW46 (OC-12 OLIU) (R1.1)
Low Speed Installation
(Optional)
Follow this procedure only if installing LNW46 (OC-12 OLIU)
(Supported starting in release R1.1) circuit packs into the Metropolis
®
DMXtend shelf.
Step 1
Refer to the engineering job specification. Identify the proper function
group(s) and/or growth slot(s) where LNW46 (OC-12 OLIU) circuit
pack will be installed.
............................................................................................................................................................................
Step 2
Remove the LNW46 (OC-12 OLIU) from the packing material.
............................................................................................................................................................................
Step 3
Place the circuit pack into the shelf (slot D1 or G1 as required). Do
NOT engage the circuit pack in the backplane connector.
............................................................................................................................................................................
Step 4
If a companion circuit pack is required, continue with the Step 5. If not,
install a 177D or LNW98 Apparatus Blank into the protection circuit
pack slot (D2 or G2 as required), then proceed to Step 7.
Important!
177D or LNW98 Apparatus Blanks are required in all
unused slots D and G to provide proper air flow for cooling.
............................................................................................................................................................................
Step 5
Remove the second LNW46 (OC-12 OLIU) from the packing material.
............................................................................................................................................................................
Step 6
Place the circuit pack into the shelf (slot D2 or G2 as required).
............................................................................................................................................................................
Step 7
Repeat Step 1 through Step 6 for each additional function group and/or
growth slot to be equipped with LNW46 (OC-12 OLIU) circuit packs.
............................................................................................................................................................................
Step 8
Check off the appropriate box in Appendix E, Installation Checklist.
...........................................................................................................................................................................
End of Steps