Lucent Technologies Galaxy Power System 4804AP H569-450
15 - 12 Troubleshooting Vector Systems
Issue 1 June 2000
Controller
LED
Controller
Alarm
Status
Vector
Controller
Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)
RECT
MIN
rFA
ALM
ICS
IP5
IP6
IP7
Internal
rectifier failure
1. Place the ac
circuit breaker
for the rectifier
in the OFF
position.
2. Remove the
rectifier from
the shelf.
3. Wait for 30
seconds or until
all front panel
display LEDs
have
extinguished.
4. Replace the
rectifier.
5. Return the ac
breaker to the
ON position.
6. Place the
rectifier ON/
STBY switch
into the ON
position.
7. If the problem
is not corrected,
replace the
rectifier.
Table 15-E: Rectifier Related Alarms
(See Figures 13-6 and 13-8)