14 - 16 Troubleshooting Millennium Systems
Issue 1 June 2000
Table 14-E: Rectifier Related Alarms
(See Figures 13-6 and 13-8)
Controller
LED
Controller
Alarm
Status
Millennium
Controller
Display
Rectifier
LED
Rectifier
Display
Possible
Problem(s)
Possible Solution(s)
RECT
MIN
Rectifier Fail
ALM
ICS
IP5
IP6
IP7
Internal
rectifier
failure
1. Place the ac
circuit breaker for
the rectifier in the
OFF position.
2. Remover the
rectifier from the
shelf.
3. Wait for 30
seconds or until
all front panel
display LEDs
have extinguished.
4. Replace the
rectifier.
5. Return the ac
breaker to the ON
position.
6. Place the rectifier
ON/STBY switch
into the ON
position.
7. If the problem is
not corrected,
replace the
rectifier.
RECT
MIN
Rectifier Fail
ALM
FSE
Fuse alarm:
• DC fuse
open
• Internal
rectifier
failure
1. Toggle the ON/
STBY switch into
the STBY position
and then back
into the ON
position.
2. If the problem is
not corrected,
replace the
rectifier.