11 - 50 Installation
Issue 1 June 2000
Power Up and Installation Completion, continued
Setting the System
Float Voltage
Setting the System
Shunt
Setting the System Float Voltage
Step
Action
1
Enter the appropriate key sequence:
•
Galaxy Millennium controllers:
Main
→
Config
→
Rect Mngr
→
Enter
•
Galaxy Vector controllers:
Config
→
Up arrow key (until FSP is on the display)
→
Enter
2
Verify that the HFV and HVSD alarm thresholds are set above
the float voltage to be specified in Step 3.
3
Use the adjust keys to set the system float voltage.
Setting the System Shunt
Step
Action
1
Enter the appropriate key sequence:
•
Galaxy Millennium controllers:
Main
→
Config
→
Shunt Type
→
Enter
•
Galaxy Vector controllers:
Config
→
Up arrow key (until Styp is on the display)
→
Enter
2
Select the Shunt type: None, Load, or Battery
“None” for Galaxy Millennium Controller
“0” for Galaxy Vector Controller