Lucent Technologies Galaxy Power System 4804AP H569-450
Issue 1 June 2000
Troubleshooting Vector Systems 15 - 15
BD LED or No
LED
Table 15-F: Miscellaneous Alarms
Controller
LED
Controller
Alarm
Status
Vector
Controller Display
Other
Indication(s)
Possible
Problem(s)
Possible Solution(s)
BD
MAJ
bod
Rectifiers
may say
ACF.
Temporary
condition that
may be
associated with
other alarms
Call your local
RTAC
representative.
None
MAJ
AUJ
Auxiliary
equipment
may have
alarm.
Problem with
operation of
auxiliary
equipment
Call your local
RTAC
representative.
None
None
None
Red LED is
lit on some
battery
contactor
drive
boards,
while green
LED is lit on
others.
If a green LED
is lit despite a
contactor open
command
issued by the
controller, the
drive card or the
contactor has
failed.
Call your local
RTAC
representative.
None
None
None
--
Fuse has
operated.
Replace the
controller fuse
labeled F1 (power).