Lucent Technologies Galaxy Power System 4804AP H569-450
Issue 1 June 2000
Installation 11 - 47
Power Up and Installation Completion, continued
Initial Power Up of the System, continued
Step
Action
8
Verify the following:
•
Green LEDs are illuminated on the rectifier and LVLD
and LVBD contactor control boards.(Alarm Card)
•
The system voltage is 52.08 volts (48V system).
•
The system current is zero.
•
The controller’s RECT and MAJ LEDs illuminate.
•
The controller’s audible alarm (if equipped) is sounding.
•
The controller display indicates one warning.
9
Turn OFF the controller’s audible alarm (if equipped).
Note: This alarm will retire on its own after the rectifier ID is
set in Step 10.
10
To set the rectifier slot ID number, follow these steps:
a. Depress and hold the rectifier’s power switch in the UP
position for approximately five seconds. The number
displayed will begin to blink, indicating that a new ID can be
set.
b. To set the ID, depress and release the switch until the
desired ID number is reached.
c. Once the desired ID number is reached, continue to hold
the switch depressed until the display stops blinking. The new
ID number is now set.
Note: Abandoning this process before the display stops
blinking will default the ID to the last number set.
11
Follow Step 2 to install the remaining rectifiers, and follow
Step 10 to set their ID numbers.
12
Verify that the system voltage again reads 52.08 volts.