Chapter 11 Maintenance
11-1
Chapter 11 Maintenance
To keep the XGT Panel best, examine the XGT Panel.
11.1 Maintenance
Because an error may be developed by environment, the periodic maintenance is needed. You should check the following
categories once or twice every 6 months.
Maintenance category
Criterion
Action
Power
Within the power change range
(Within
15% / +10%)
Modify the source of electric power in order to be in
the fluctuation range of a permissible voltage.
Environment
Operating
temperature
0 ~ + 50
℃
Modify the operating temperature and humidity to be
proper.
Operating
humidity
10 ~ 85%RH
Vibration
No vibration
Use the anti-vibration rubber and make a count
measure.
Getting loose of power terminal There is no unwinding
Screw the unwound terminal.
Getting loose of
communication connector
There is no unwinding
Screw the unwound terminal.
Reserved part
Amount of reserved part and
reservation
Check the status
Refill the insufficiency and improve the reservation.
Gasket installation status
No gap between the gasket and
panel.
Replace gasket or affix brackets firmly
Gasket status
No damage or deterioration
Replace gasket
11.2 Daily Maintenance
Check the followings daily.
Maintenance category
Maintenance contents
Criterion
Action
Mounting status
Check the brackets
Should be mounted firmly
Retighten screws
Power terminal status
Loose terminal screws
Not loose
Retighten screws
Reduce the distance between
compressed terminals.
Keep the proper distance.
Correction
Communication connector
status
Unwinding of fixed screw
Not loose
Retighten screws
Indication LED
Check the lighting
Blue LED should be turned on
Refer to the appendix 1.
Summary of Contents for eXP2 Series
Page 25: ......
Page 38: ...Chapter 4 System Configuration 4 7 2 General ...
Page 41: ...Chapter 4 System Configuration 4 10 4 Printer ...
Page 57: ......
Page 73: ......
Page 81: ......
Page 95: ......
Page 123: ......
Page 124: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 eXP2 04X0D ...