Chapter 10 Installation and Wiring
10-5
Remark
(1) Must be used the gasket to prevent dust or other contaminant ingress.
(2) When mounting at the panel, if the surface of panel is uneven, water or dust can enter the machine
through the gaps. As such problems can occur depending on the thickness and material (steel, aluminum,
acrylic and etc.) of the panel, it is required to review the installation environment. Also it is necessary to
check if Gasket and the panel are closely contacted together.
(3) When Gasket is contaminated or damaged by the deterioration after the use for a certain period of time,
the waterproof/dustproof effect can be noticeably weakened. In case when Gasket should be replaced,
contact the agency or a sales office close by.
(3) Installation location
When installing the XGT Panel, consider screen and use of touch.
When you don’t see within the following angle, you may not see clearly. When installing, consider angle.
Item
Left and Right
Upper
Lower
eXP2-0400D
60 deg.
40 deg.
50 deg.
eXP2-0500D
eXP2-0502D
60 deg.
40 deg.
60 deg.
eXP2-0700D
eXP2-0701D
eXP2-0702D
70 deg.
50 deg.
70 deg.
eXP2-1000D
eXP2-1001D
(4) Fixing
Fix XGT Panel to the panel using the supplied brackets provided in the packaging.
Panel
Fix bracket
Fix bracket
Fix bracket
Fix bracket
Summary of Contents for eXP2 Series
Page 25: ......
Page 38: ...Chapter 4 System Configuration 4 7 2 General ...
Page 41: ...Chapter 4 System Configuration 4 10 4 Printer ...
Page 57: ......
Page 73: ......
Page 81: ......
Page 95: ......
Page 123: ......
Page 124: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 eXP2 04X0D ...