Chapter 2 System Configuration
2-8
Items
Items
Items
⑥
USB Host
1) USB Memory Connection: Backup of data such as alarm/logging/recipe
and storage of screen data, Send/Receive project data, Send XP-Runtime
2)
User’s Interface Connection: Using mouse/keyboard
3) Printer connection: Printing function
* Rated 5 VDC, Typical 100mA
⑦
Battery Cover
Reset Switch
Backup Battery
Setting Switch
<Setting Switch Configuration >
NO.1
A Side.
Backup Battery On
B Side.
Backup Battery Off(Default)
NO.2/3
A Side.
COM1 RS-485 Terminating Resistance On
(Default)
B Side.
COM1 RS-485 Terminating Resistance Off
NO.4/5
A Side.
COM3 RS-422 Terminating Resistance On
(Default)
B Side.
COM3 RS-422 Terminating Resistance Off
⑧
Power Terminal
Composed of Power Input(DC24V) and FG Terminal
⑨
Ethernet Terminal
Ethernet: 10Base-T/ 100Base-TX
1) Send Project Data
2) Receive backup data and project file
3) Send XP-Runtime
4) PLC/Control Device Communication
⑩
COM3 Connector
RS-422/485: PLC or Control Device Communication
⑪
COM1, COM2
Connector
RS-485, RS-232C: PLC or Control Device Communication
Remark
(1) For further details on connection of communication, please refer to Communication Instruction Manual.
(2) For further details on installation, please refer to the Chapter 10.
A. Reset Switch
B. Coin Battery
C. Setting Switch
Summary of Contents for eXP2 Series
Page 25: ......
Page 38: ...Chapter 4 System Configuration 4 7 2 General ...
Page 41: ...Chapter 4 System Configuration 4 10 4 Printer ...
Page 57: ......
Page 73: ......
Page 81: ......
Page 95: ......
Page 123: ......
Page 124: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 eXP2 04X0D ...