
Chapter 2 System Configuration
2-4
Items
Part Names
Descriptions
⑦
Battery Cover
Reset Switch
Backup Battery
Setting Switch
<Setting Switch>
No.1
A Side.
Backup Battery On
B Side.
Backup Battery Off(Default)
No.2 / 3
A Side.
RS-422/485 Terminating Resistance On
(Default)
B Side.
RS-422/485 Terminating Resistance Off
No. 4
A Side.
O/S Download Mode
B Side.
Operating Mode(Default)
⑧
Ethernet Terminal
Ethernet: 10Base-T/ 100Base-TX
1) Send Project Data
2) Receive backup data and project file
3) Send XP-Runtime
4) PLC/Control Device Communication
⑨
RS-232C, RS-
422/485 Connector
RS-232C (COM2): PLC/ Control Device Communication
RS-422/485 (COM3): PLC/ Control Device Communication
※
COM1 is not used.
Summary of Contents for eXP2 Series
Page 25: ......
Page 38: ...Chapter 4 System Configuration 4 7 2 General ...
Page 41: ...Chapter 4 System Configuration 4 10 4 Printer ...
Page 57: ......
Page 73: ......
Page 81: ......
Page 95: ......
Page 123: ......
Page 124: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 eXP2 04X0D ...