Chapter 3 Standard Specification
3-1
Chapter 3 Standard Specification
3.1 General Standards
XGT Panel general standard is as follows.
No.
Category
Standard
Related
standard
1
Ambient
operating
temperature
0
℃∼
+50
℃
-
2
Storage
temperature
-20
℃∼
+60
℃
-
3
Operating
humidity
10
∼
85%RH, non-condensing.
-
4
Storage humidity
10
∼
85%RH, non-condensing.
-
5
Vibration
resistance
Occasional vibration
count
-
Frequency
Acceleration
Amplitude
10 times each in X,
Y and Z direction
IEC 61131-2
5≤f< Hz
-
3.5mm
9≤f≤150 Hz
9.8m/s
2
-
Continuous vibration
Frequency
Acceleration
Amplitude
5≤f< 9 Hz
-
1.75mm
9≤f≤150 Hz
4.9m/s
2
-
6
Shock
endurance
* Maximum shock acceleration: 147m/s
2
(15G)
* Duration time: 11ms
* Pulse wave: half sine pulse (3 times each in X, Y and Z directions)
IEC 61131-2
7
Noise
Immunity
Square wave
Impulse noise
DC: ±1,200V
LS ELECTRIC
Standard
Electrostatic
Discharge
Immunity
±6 kV(Contact Discharge),
±8 kV(Air Discharge)
IEC 61131-2
IEC 61000-4-2
Electromagnetic
Radiated
Emissions
80 ~ 1,000 MHz, 10 V/m
IEC 61131-2
IEC 61000-4-3
Electrical Fast
Transient & Burst
Immunity
Category
Power module
Communication
Interface
IEC 61131-2
IEC 61000-4-4
Voltage
2.4 kV
1.2 kV
8
Environment
Free from corrosive gases and excessive dust
-
9
Operating height
Up to 2,000m(6,562ft)
-
10
Pollution degree
2 or less
-
11
Cooling method
Natural Air-Cooling
-
Summary of Contents for eXP2 Series
Page 25: ......
Page 38: ...Chapter 4 System Configuration 4 7 2 General ...
Page 41: ...Chapter 4 System Configuration 4 10 4 Printer ...
Page 57: ......
Page 73: ......
Page 81: ......
Page 95: ......
Page 123: ......
Page 124: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 eXP2 04X0D ...