Detailed Specification of Communication Profile Specific Objects
27
5.9 Life Time Factor
This SDO sets the Life Time Factor when using the Node Guarding protocol as the
Error Control protocol.
Index
0x100D
Data type
UNSIGNED8
Sub-index
0x00
Access
RW
Data
This factor is used to calculate the Node Life Time. It is set to
"0" when the Node Guarding protocol is not used.
5.10 COB-ID EMCY
This SDO sets the CAN-ID of the Emergency frame. This SDO is read-only, and
cannot be modified for the G100 CANopen communication module.
Index
0x1014
Data type
UNSIGNED32
Sub-index
0x00
Access
RW
Data
$0x80($Node ID is the FBus ID currently set in the
communication module.)
5.11 Producer Heartbeat Time
This SDO indicates the interval of the Heartbeat transmission.
Index
0x1017
Data type
UNSIGNED16
Sub-index
0x00
Access
RW
Data
Set time in msec units.