Profile
32
The bits between bit 4 and bit 7 are command bits that are operated in Operation
Mode.
Bit
Value
Description
4 (Enable Ramp)
0
Maintain the previous operational
state
1
Operate the inverter by the command
bits
5 (Unlock Ramp)
0
Hold the output frequency
1
Drive up to the target frequency
6 (Reference Ramp)
0
Set the target frequency to "0"
1
Set as the target frequency
8 (Halt)
X
Not used
▶
Status Word (Object: 0x6041)
This object indicates the current state of the current device.
Index
Sub-index
Name
Type
Property
Unit
Range
0x6041
-
Status
word
U16
RO
-
-
This object is not available if "CM-11 (Profile Sel)" is set to "1 (LS Device Profile (PDO3))."
The bit composition below presents the command by bits of the Status Word.
Bit
Description
0
Ready to switch on
1
Switched on
2
Operation enabled
3
Fault (Trip)
4
Voltage enable
5
Quick stop
6
Switch on disable
7
Warning
8
Not used
9
Remote
10
Target reached
11
Internal limit active
12
–15
Not used
The table below presents the bit values for Bits 0
–3, Bit 5, and Bit 6 by the device's FSA state.