30
6.1.2 CiA 402 SDO
▶
Error codes (Object : 0x603F)
When the inverter has tripped, this object is used to identify the type of trip.
Index
Sub-index
Name
Type
Property
Unit
Range
0x603F
-
Error code
U16
R
-
-
The table below presents the error code numbers that are returned for the inverter
trips.
Value
Description
Value
Description
Data
0x0000
None
0x7120
No Motor Trip
0x1000
Untitled
0x8401
Speed Dev Trip
0x2220
Inverter OLT
0x8402
Over Speed
0x2310
OverCurrent1
0x9001
External Trip
0x2330
Ground Trip
0x9002
BX
0x2340
OverCurrent2
0xFF01
Ethermal
0x3130
In Phase Open
0xFF03
Out Phase Open
0x3210
Over Voltage
0xFF04
Over Load
0x3220
Low Voltage
0xFF05
Under Load
0x4000
NTC Open
0xFF06
Thermal Trip
0x4310
Over Heat
0xFF07
Pre PID Fail
0x5000
HW Diag
0xFF0A
Lost Command
0x5450
Fuse Open
-
-
▶
Control Word (Object: 0x6040)
This object used to operate the inverter.
Index
Sub-index
Name
Type
Property
Unit
Range
0x6040
-
Control
word
U16
RW
-
-
This object is not available if "CM-11 (Profile Sel)" is set to "1 (LS Device Profile (PDO3))."