146
PD-27
CM5
The display content of Condition Monitoring
Register 5 is selected.
Communication
address:
0336H
0337H
Initial value
0
Control mode
ALL
Unit
N/A
Configuration range
0 ~ 18
Data size
16bit
Data format
Dec
For the settings, refer to PD-21
.
PD-28
VMR1
The ratio for MON1 analog monitoring output
Communication
address:
0338H
0339H
Initial value
100
Control mode
ALL
Unit
%
Configuration range
0 ~ 100
Data size
16bit
Data format
Dec
Example:
PD-22 = 01 (MON1 is the analogue output of motor speed while MON2 is the analogue output of motor torque.)
MON1 output voltage=
8 ∗
Motor rotation speed
(
Max.speed
∗
PD
−
28
100
)
unit: volts
MON2 output voltage=
8 ∗
Motor torque
(
Max.torque
∗
PD
−
29
100
)
unit: volts
PD-29
VMR2
The ratio for MON2 analog monitoring output
Communication
address:
033AH
033BH
Initial value
100
Control mode
ALL
Unit
%
Configuration range
0 ~ 100
Data size
16bit
Data format
Dec