Command Injection Mode
Block diagram of the serial interface in command injection mode
In this mode, the receiver works as an RS-232 bidirectional converter. The TPS signal is converted to RS-232
dataandviceversa.TCP/IPportnumbersaredefinedfortheserialports(TPSandlocal)forthispurpose.
E.g. the default Command Injection port number of the local RS -232 port is 8001. If a command is coming
from the TPS interface which addresses to the port no. 8001, it will be transmitted to the Tx pin of the
local RS-232 port. That works in the opposite direction of course and the method is the same on the serial
interface of the TPS port as well.
RS-232 Signal Transmission – Example
The Concept
The System controller can send commands to the receiver through the TPS transmitter and is able to remote
control the projector via RS-232.
Settings
▪
System controller
:wirelessIPconnectiontothesameEthernetasthetransmitterisconnectedto.Use
adedicatedsoftwaretool(e.g.aterminal)whichissuitableforsendingcommandsviaTCP/IPtoa
certainIP:portaddress.
▪
Transmitter
:settheRS-232modetoCommandInjectiononTPSoutputport.Setthefurtherparameters
(Baudrate,Databits,etc.)inaccordancewiththespecificationsoftheprojector.Thetransmitterwill
transmit the RS-232 data toward the receiver.
▪
Receiver
:settheRS-232modetoPass-throughonRS-232port.
▪
Projector
:notetheRS-232portsettingthatisspecifiedbytheManufacturer.Connectasuitableserial
cable with the proper wiring.
4.6.2.
RS-232 Recognizer
DIFFERENCE:
This feature is available only in HDMI-TPS-RX110AY-Plus model.
Whenthe
HDMI-TPS-RX110AY-Plus
hasanactivevideosignal,thereceiverlogintheVCcodecautomatically.
Steps and Settings
Process
Settings
WhensignalpresentsonanyHDMIinput,the
extendersendsamessage:'
ping
'.
This condition and the action is set in Event manager.
The serial communication is scanned continuously by the
recognizer in the extender and gets the '
Login name
' string.
Videocodecsendsamessage:'
Login name:
'.
When'
Login name:
' is detected in the string, the
extendersendsamessage:'
Admin
'.
This condition and the action is set in Event manager.
The serial communication is scanned continuously by
the recognizer in the extender and gets the '
Password
'
string.
Videocodecsendsamessage:'
Password:
'.
When'
Password:
' is detected in the string, the
extendersendsamessage:'
Admin
'.
This condition and the action is set in Event manager.
Loginisestablished,Videocodecisreadytouse.
First,configuretherecognizerfortheserialcommunication,afterthat,settheeventsintheEventManager(for
more details see the
section).TheRS-232recognizersettingshastobedonewithLightware
Device Controller Software (see the
section)orwithLW3protocolcommands(seethe
section).
Settings in the Event manager
▪
E1.
WhenthesignalispresentonO1portofthe
HDMI-TPS-RX110AY-Plus, it sends a message
'PING'
on
P1portofRS-232totheVCcodec.FormoredetailsseeMessageSendingviaRS-232SerialPortsection.
▪
E2
. Set a condition where '
Login name:
' is the recognized RS-232 message. Action is sending serial
message('Admin')ontheP1porttotheVCcodec.
▪
E3
. Set a condition where '
Password:
' is the recognized RS-232 message. Action is sending serial
message('Admin')ontheP1porttotheVCcodec.