Maintenance
92
3.
Upload the update file using the card’s user interface, see
on the next page.
a. Select the “GXT5” tab, then the File Transfer folder in the tab-menu pane on the left-hand side of the
page.
b.
On the file-transfer page, click Choose File, and select the MCU upgrade file, then click Transfer file.
c. Enter the Username and Password, then click Login.
The factory-defaults:
Username : Liebert (case-sensitive)
Password: Liebert (case-sensitive)
• The name and password may have been changed from the default. Be sure to obtain the username
and password from an administrator.
The status of the transfer displays in the File Transfer Status section. After about 2 minutes, the UPS restarts
and the web page refreshes.
• The transfer process takes about 2 minutes. Do not leave or close the page until the status is “Update
Complete.”
d.
You can check the firmware version, select the System folder in the tab-menu pane on the left-hand side
of the page, and check the Firmware Version field, see
on the next page.
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...