Operation and Display Panel
74
MESSAGE
DESCRIPTION
Remote power- on
The UPS was powered on remotely. This will display in the log whenever the event
occurs
Remote shut- off
The UPS was powered off remotely. This will display in the log whenever the event
occurs.
Remote shutdown
Any mode shutdown was initiated by the dry contact input. This will display in the log
whenever the event occurs.
REPO
Shutdown caused by the REPO terminal Normally-Closed contact input opening. This
will display in the log whenever the event occurs.
Shutdown due to over temp
During the UPS operation, the system checks that the heat sink temperature exceeds
the setting range. If over temperature, please check:
•
Ambient temperature too high or not
•
Dust is blocked or not
•
Fan fault or not
System over temp
Internal heat sink temperature too high, and the inverter is off. The alarm can only be
silenced if the heat-sink temperature is lower than the alarm setting. The system can
automatically start after over temperature fault is solved.
If over temperature, please check:
•
Ambient temperature too high or not
•
Dust is blocked or not
•
Fan fault or not
Turn on fail
The UPS does not start because there is no mains/utility power or it is outside of the
range of the voltage required to supply the full load. Check the AC input power.
UPS has no output
Both Inverter and Bypass are not supplying power due to the UPS output being turned
off remotely or via the LCD, or are unavailable due to no input power or input power out
of range. Check that UPS is on and input power is available.
4.2.7. About Screen
The About screen offers tabs that list information about the product.
•
Product tab - shows UPS identification information, firmware versions, and information about the
communication card (when the card is installed).
•
Efficiency tab - shows a curve of the efficiency of your UPS model vs the load capacity used.
•
Battery age tab - shows the curve of the percent state-of-health (SOH) of the installed battery versus time.
The UPS calculates one value per week and plots it on the graph. The values are based on the battery
temperature, age, and the actual amount of energy discharged from the battery if the battery has been
discharged fully.
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...