Vertiv | Liebert® GXT5™ | Installer/User Guide
123
Table 7-20 Battery Run Time in Minutes Model: 20-kVA.Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1
2
3
4
5
6
7
8
9
10
%
VA
W
Minutes
10
2000
2000
62.5
136.0
222.5
309.5
396.5
483.0
570.0
656.5
743.5
830.5
917.0
20
4000
4000
26.0
64.0
101.0
139.5
183.5
228.0
272.5
316.5
361.0
405.0
449.5
30
6000
6000
14.5
39.0
64.5
89.5
114.5
140.5
170.5
200.0
230.0
259.5
289.5
40
8000
8000
9.5
26.5
45.5
64.5
83.5
102.5
121.5
141.5
164.0
186.5
209.0
50
10000
10000
7.0
19.5
34.5
50.0
65.0
80.5
95.5
111.0
126.0
142.5
161.0
60
12000
12000
5.5
15.0
27.0
40.0
53.0
65.5
78.5
91.5
104.0
117.0
129.5
70
14000
14000
4.0
12.0
21.5
32.5
43.5
55.0
66.0
76.5
87.5
98.5
109.5
80
16000
16000
3.5
10.0
18.0
27.0
36.5
46.5
56.5
66.0
75.5
85.0
94.5
90
18000
18000
3.0
8.5
15.0
23.0
31.0
40.0
48.5
57.5
66.0
74.5
83.0
100
20000 20000
2.5
7.0
13.0
19.5
27.0
34.5
42.5
50.5
58.0
66.0
73.5
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...