Vertiv | Liebert® GXT5™ | Installer/User Guide
35
2.6.5. Connecting to Terminal Blocks on 16-kVA and 20-kVA models
These models offer a four types of I/O connection. One shorting cable (W01) ships installed on the terminal
block. Two additional shorting cables are included with the accessories to wire the different types Figure 2-8
below, shows the terminal block. Refer to the details in Terminal-block Connections on page 30, when making
the connections.
below, shows the 3-in 1-out split-bypass connection
below, shows the 3-in 1-out common-source connection
on the next page, shows the 1-in 1-out split-bypass connection
on the next page,, shows the 1-in 1-out common-source connection
Figure 2-8 3-in 1-out split-bypass connection
ITEM
DESCRIPTION
1
Output
2
Bypass
3
Input
Figure 2-9 3-in 1-out Common-source Connection, 16-kVA and 20-kVA models
ITEM
DESCRIPTION
1
Output
2
Bypass
3
Input
4
Shorting cable (W01), installed at factory
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...