Installation
38
Figure 2-12 Dry-contact Port and Pin Layout
• Pins 7 and 8 are shorted before delivery.
• The emergency power-off (EPO) action of the UPS closes the rectifier, inverter and static bypass, but
it cannot disconnect the UPS mains input inside. To completely disconnect the UPS, disconnect the
upstream input circuit breaker when generating the EPO. For details on REPO connection and opera-
tion, see
Connecting a Remote Emergency Power-off (REPO) Switch
Table 2-4 Dry-contact Connection and Pin-out Descriptions
PORT
NO.
PORT
NAME
PIN
NO.
PIN NAME
DESCRIPTION
1
Input 1
1
Remote Comms 1
User configurable dry-contact input that can be set to trigger
the events below. The user can also select the dry-contact as
either NO or NC. (See
) When NO, Pins 1 and 2 are shorted to trigger the event.
When NC, Pins 1 and 2 are opened to trigger the event.
Options are:
•
Disable (default)
•
Battery mode shutdown - If the UPS is running on batteries
and this input is triggered, the UPS shuts down
•
Any mode shutdown - If this input is triggered, the UPS
shuts down regardless of current operating mode
•
Maintenance mode-For 16 & 20 kVA model, If this input is
triggered, it means the UPS is in maintenance mode.
2.
Signal Ground
Signal Ground
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...