118
7.1. Battery Run Times
• Run times in this table are approximate. Times are based on new, fully-charged, standard battery mod-
ules at a temperature of 77 °F (25 °C) with 100% resistive UPS loading. Run times listed above can vary
by ±5% due to manufacturing variances of the individual batteries.
Table 7-10 Battery Run Time, 750 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1
2
3
4
5
6
7
8
9
10
%
VA
W
Minutes
10
75
75
135.4
444.1
770.8
1123.4
1452.2
1695.4
1863.8
1987.3
2081.7
2156.3
2216.6
20
150
150
68.0
229.0
401.4
581.6
760.5
952.0
1147.8
1330.7
1499.7
1635.5
1745.4
30
225
225
44.1
163.7
281.7
407.9
537.8
663.9
800.6
939.7
1080.9
1221.8
1350.2
40
300
300
33.7
127.1
218.3
316.1
416.5
519.9
620.3
724.8
833.9
944.6
1056.5
50
375
375
25.7
103.2
178.9
255.9
337.1
420.2
505.5
592.1
672.6
761.7
852.0
60
450
450
20.4
84.8
149.0
212.4
280.7
350.0
420.3
492.6
565.3
631.7
706.8
70
525
525
16.7
72.0
128.2
183.8
238.8
298.1
358.3
419.6
481.8
544.9
607.0
80
600
600
14.1
59.7
112.1
161.6
208.6
260.6
313.2
366.4
420.4
475.8
531.1
90
675
675
12.1
53.0
99.5
143.9
188.3
232.1
278.8
326.1
374.6
423.3
473.1
100
750
750
10.5
46.3
88.3
130.2
170.8
208.8
251.5
294.1
337.6
381.7
426.5
Table 7-11 Battery Run Time, 1000 VA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1
2
3
4
5
6
7
8
9
10
%
VA
W
Minutes
10
100
100
101.8
332.7
584.9
841.2
1114.7
1373.2
1590.9
1750.8
1873.0
1969.6
2047.7
20
200
200
50.1
179.8
311.9
453.2
595.8
736.7
888.2
1042.4
1199.1
1340.5
1476.5
30
300
300
33.7
127.1
218.3
316.1
416.5
519.9
620.3
724.8
833.9
944.6
1056.5
40
400
400
23.8
95.8
168.9
239.3
316.4
394.3
474.5
555.3
629.9
713.6
798.3
50
500
500
17.8
76.3
135.1
193.0
251.8
314.0
377.3
443.1
506.8
573.0
632.6
60
600
600
14.1
59.7
112.1
161.6
208.6
260.6
313.2
366.4
420.4
475.8
531.1
70
700
700
11.5
50.7
95.3
139.4
181.7
224.1
268.6
315.0
361.0
408.6
457.6
80
800
800
9.6
43.3
83.4
120.8
160.1
197.6
235.3
275.3
316.3
357.1
399.0
90
900
900
8.1
38.2
73.0
107.4
141.0
174.8
206.9
241.5
277.6
314.0
350.4
100
1000
1000
6.8
33.3
62.8
94.6
125.7
156.3
187.0
216.1
248.0
280.4
313.1
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...