Vertiv | Liebert® GXT5™ | Installer/User Guide
109
MODEL GXT5-
3000IRT2UXL*
3000IRT2UXLE
RATING
3000 VA/3000 W
Environmental Requirements
Operating Temperature,
°F (°C)
+32 to +122 (0 to 50); Operating temperature may be increased to 122 °F (50 °C with a 10%
derating of the output power
Storage Temperature, °F
(°C)
-4 to +140 (-20 to 60)( contain batteries will be from -15 to 40 °C.)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000 m) at 77ºF (25ºC) without derating
Audible Noise
<48 dBA max @ 3 ft. (1 m) front and sides <48 dBA max @ 3 ft. (1 m) rear
Agency
Safety
Transportation
ISTA Procedure 1A
Surge Immunity
ANSI C62.41 Category B
RFI/EMI
CISPR22 Class A (RFI)/ FCC Part 15 (Class A)
*Only these models are available in the ASIA PACIFIC region.
Table 7-4 UPS Specifications, 5-kVA and 6-kVA models
MODEL GXT5-
5000IRT5UXLN*
5000IRT5UXLE
6000IRT5UXLN*
6000IRT5UXLE
RATING
5000 VA/5000 W
6000 VA/6000 W
Dimensions, D×W×H, in. (mm)
Unit
430 × 630 × 217 (16.9 × 24.8 × 8.5)
Shipping
600 × 800 × 520 (23.6 × 31.5 × 20.5)
Weight,
kg
(
lb
)
Unit
70.8 (156)
70.8 (156)
Shipping
92 (202.8)
89 (196.2)
92 (202.8)
89 (196.2)
Input AC Parameters
Operating Frequency,
Nom.
50 or 60 Hz (factory-default is 50 Hz)
Factory-default VAC
230 VAC
Operating voltage
range without battery
operation
176 to 288 VAC (100 – 176 VAC with power derating)
Maximum Allowable VAC
288 VAC
Input frequency without
battery
operation
40 to 70 Hz
Input Power Connection
PD5-CE6HDWRMBS
PD5-CE6HDWRMBS
UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...