Specifications
110
MODEL GXT5-
5000IRT5UXLN*
5000IRT5UXLE
6000IRT5UXLN*
6000IRT5UXLE
RATING
5000 VA/5000 W
6000 VA/6000 W
Output AC Parameters
AC-AC Efficiency
94%
Factory-default VAC
Frequency
230 VAC, 50 Hz
Output Power
Connection
PD5-CE6HDWRMBS
PD5-CE6HDWRMBS
Waveform
Sinewave
Main Mode Overload
> 150% minimum 200 mS, 125 to 150% for 60 seconds;
105 to 125% for 5 minutes; ≤ 105% continuous
User-configurable VAC
200/208/220/230/240 VAC
(Adjustable using operation/display configuration options)
Bypass parameters
Upper-limit selections
+10%, +15%, +20%; d10%.
Lower-limit selections
-10%, -15%, -20%; default -15%
Disable-bypass
operation
When the input frequency prevents synchronous operation.
Internal Battery Charger
Charger Current, A
default 2.25 A
,
maximum 5 A
Battery Parameters
Type
Valve-regulated, non-spillable, lead acid
Qty×V×Rating
16 x 12V x 9.0AH
Battery Mfr./Part#
9AH; LEOCH/DJW12-9.0
Back-up time
See
See
.
Environmental Requirements
Operating Temperature,
°F (°C)
0 to 40 (32 to 104) (no derating)
Storage Temperature, °F
(°C)
-20 to +60 (-4 to +140) ( contain batteries will be from -15 to 40 °C.)
Relative Humidity
0 to 95% non-condensing
Operating Elevation
Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating
Audible Noise
Front and Side <55 dBA
Agency
Safety
*
IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
EMI/EMC/C-Tick EMC
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A)
CISPR22 Class A (RFI)
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...