106
MODEL GXT5-
750IRT2UXL*
750IRT2UXLE
1000IRT2UXL*
1000IRT2UXLE
RATING
750 VA/750 W
1000 VA/1000 W
Environmental Requirements
Operating Temperature,
°F (°C)
+32 to +122 (0 to 50); Operating temperature may be increased to 122 °F (50 °C with a 10%
derating of the output power)
Storage Temperature, °F
(°C)
-4 to +140 (-20 to 60) ( contain batteries will be from -15 to 40 °C.)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000 m) at 77 ºF (25 ºC) without derating
Audible Noise
<46 dBA max @ 3 ft. (1 m) front and sides <43 dBA max @ 3 ft. (1 m) rear
Agency
Safety
UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
Transportation
ISTA Procedure 1A
Surge Immunity
ANSI C62.41 Category B
RFI/EMI
CISPR22 Class A (RFI)/ FCC Part 15 (Class A)
*Only these models are available in the ASIA PACIFIC region.
Table 7-2 UPS Specifications, 1500 VA and 2000 VA Models
MODEL GXT5-
1500IRT2UXL*
1500IRT2UXLE
2000IRT2UXL*
2000IRT2UXLE
RATING
1500 VA/1500 W
2
000 VA/
2
000 W
Dimensions, D×W×H, in. (mm)
Unit
18.5 × 16.9 × 3.4 (470 × 430 × 85)
Shipping
24.3 ×22.4 x 10.3 (617 x 570 x 262)
Weight,
kg
(
lb
)
Unit
21 (
46.2
)
Shipping
28 (
61.6
)
25.5
(
56.1
)
28
(
61.6
)
25.5
(
56.1
)
Input AC
Voltage Range (typical)
230 VAC nominal; variable based on output load
90% ~ 100% loading
168 to 288 VAC
70% ~ 90% loading
150 to 288 VAC
50%~70% loading
115 to 288 VAC
0%~50%
115 to 288 VAC
Frequency
40 Hz to 70 Hz; Auto Sensing
Input Power Cord
C14
C20
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...