Installation
42
2.7.6. Connecting Liebert IRM sensors
The GXT5 supports up to 40 Liebert® IRM sensors (The sensor address must be 1~40). Available sensor
types include temperature
,
and
temperature &
humidity sensors.
The highest sensor data can be shown in GXT5/battery status page. And the highest temperature from the
sensors can be used for battery temperature compensation.
To install an Liebert IRM sensor:
1. Connect the sensor and the RS-485 port using network cable.
2. Place the sensor into the groove of the EBC, as shown in
.
2.8. Installing a Parallel System
10-kVA, 16-kVA, and 20-kVA models may be configured in a parallel system. The UPS parallel system provides
support to the following options:
•
2 active systems
•
2 active systems plus 1 redundant system
•
1 active system plus 1 redundant system
All electrical requirements, including external-distribution panel and branch circuit breaker, apply to each UPS
in a parallel system, which are then connected in ring configuration for redundancy and additional reliability.
System load information can be accessed via any controller/display in the system.
The following are requirements for the parallel-connected system:
•
Each UPS must have the same capacity and must be connected to the same mains/utility source.
•
If a residual-current detector (RCD) is required,
it
must be correctly-set and installed before the same
neutral-line input terminal. See safety and regulatory information, available at
•
The output of each
UPS
must be connected to the same output bus.
•
The parameter configuration for each UPS must be
identical
.
•
Because the parallel system is not fitted with auxiliary-contact detection devices for the output circuit
breaker or the maintenance-bypass circuit breaker of each UPS, You must strictly-follow the procedures
for transferring between operating modes when removing a single UPS from the parallel system before
maintenance and when adding a single UPS after maintenance. Failure to observe the procedures may affect
the reliability of the load power supply.
on the next page shows an example of the 10-kVA model connected as a 2 + 1 parallel system
connected in a ring configuration.
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...