Installation Places
Installation Manual
11
ENGLISH
CAUTION : In case that the unit is installed near the sea, the installation parts
may be corroded by salt, The installation parts (and the unit) should be taken
appropriate anti-corrosion measures.
[Inspection Hole Standard]
Number of
Inspection hole
Distance between
False ceiling & Actual ceiling
Remarks
1
More than 100 cm
Sufficient space in the ceiling for servicing.
2
20 cm to 100 cm
Insufficient space. Difficult for servicing
Hole size should be more
than the size of IDU.
Less than 20 cm
Minimum height for motor replacement.
Ceiling Concealed Duct – H-INV
Ceiling Concealed Duct – High Static
Top view
(unit: mm)
Front view
Top view
(unit: mm)
Front view
H
Front
Inspection hole
(600 x 600)
Control box
1 000
H
600
600
Front
Inspection hole (600X600)
Control box